• Ensure that the rack is level and stable before extending a component from the rack.
• Ensure that proper airflow is provided to the components in the rack.
• Do not step or stand on any component or system when servicing other systems or components in a rack.
• When mounting the Cisco Catalyst 8500 Series Edge Platforms in a partially filled rack, load the rack
from the bottom to the top with the heaviest component at the bottom of the rack.
• If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the
unit in the rack.
General Rack-Selection Guidelines
The Cisco Catalyst 8500 Series Edge Platforms can be mounted in most two-post or four-post, 19-in. equipment
racks that comply with the Electronics Industries Association (EIA) standard for equipment racks (EIA-310-D
19-in.). The rack must have at least two posts with mounting flanges to mount the chassis.
When mounting a chassis in any type of rack equipment, ensure that the inlet air to the chassis does not exceed
131°F (55°C).
Caution
The distance between the center lines of the mounting holes on the two mounting posts must be 18.31 in. ±
0.06 in. (46.50 cm ± 0.15 cm). The rack-mounting hardware included with the chassis is suitable for most
19-in. (48.3-cm) equipment racks.
Consider installing the Cisco Catalyst 8500 Series Edge Platforms in a rack with the following features:
• NEBS-compliant, 19-in. (48.3-cm) wide rack.
• EIA or ETSI hole patterns in the mounting rails. Required mounting hardware is shipped with the Cisco
Catalyst 8500 Series Edge Platforms. If the rack that you plan to install the system in has metric-threaded
rails, you must provide your own metric-mounting hardware.
• Perforated top and open bottom for ventilation to prevent overheating.
• Leveling feet for stability.
The Cisco Catalyst 8500 Series Edge Platforms should
not
be installed in an enclosed rack because the chassis
requires an unobstructed flow of cooling air to maintain acceptable operating temperatures for its internal
components. Installing the router in any type of enclosed rack—
even with the front and back doors
removed
—could disrupt the air flow, trap heat next to the chassis, and cause an overtemperature condition
inside the router. If you use an enclosed rack, make certain that there are air vents on all sides of the rack and
there is proper ventilation.
Note
Guidelines for 23-in. (Telco) Racks
If needed, you can also install the Cisco Catalyst 8500 Series Edge Platforms in 23-in. (Telco) racks. For
information on the adapters needed for 23 in. racks, contact the Newton Instrument Company: