Verifying Rack Dimensions
Before you install the chassis, measure the space between the vertical mounting flanges (rails) on your
equipment rack to verify that the rack conforms to the measurements shown in the following image.
SUMMARY STEPS
1.
Mark and measure the distance between the holes on the left and right mounting rails.
2.
Measure the space between the inner edges of the left front and right front mounting flanges on the
equipment rack.
DETAILED STEPS
Step 1
Mark and measure the distance between the holes on the left and right mounting rails.
The distance should measure 18.31 inches ± 0.06 inches (46.5 cm ± 0.15 cm).
Measure for pairs of holes near the bottom, middle, and top of the equipment rack to ensure that the rack posts
are parallel.
Note
Step 2
Measure the space between the inner edges of the left front and right front mounting flanges on the equipment rack.
The space must be at least 17.7 inches (45 cm) to accommodate the chassis that is 17.25 inches (43.8 cm) wide and fits
between the mounting posts on the rack.
Figure 10: Verifying the Equipment Rack Dimensions
Attaching the Chassis Rack Mount Brackets
This section explains how to attach the front and rear rack mount brackets to the chassis. Before installing the
chassis in the rack, you must install the rack mount brackets on each side of the chassis.
The parts and tools required for installing the rack mount brackets and cable management brackets are listed
in the
“Tools and Equipment” section on page 5-23
Cisco ASR 1002-X Router Overview and Installation
17
Cisco ASR 1002-X Router Overview and Installation
Verifying Rack Dimensions