8.
Screw the cable management bracket to each side of the rack mount brackets already attached to the
chassis. Use two screws for each cable management bracket. Use the packet of four screws.
9.
Verify if all the screws are securely tightened.
10.
Go to the
Attaching a Chassis Ground Connection, on page 26
to continue the installation.
DETAILED STEPS
Step 1
Remove debris and dust, if any, from the tabletop or platform, as well as from the surrounding area.
Step 2
Lift the chassis into position on the equipment shelf or tabletop (see following figure).
At least two people are required to lift the chassis onto a tabletop or platform. To prevent injury, keep your back straight
and lift with your legs, not your back. Statement 164
Figure 8: Lifting the Chassis
The chassis in the image does
not
represent the Cisco ASR 1002-X Router.
Step 3
Attach the front rack mount brackets. Locate the threaded holes in the front sides of the chassis (first holes beyond the
vent holes).
Step 4
Align the front rack mount bracket to one side of the chassis.
Step 5
Insert and tighten the black screws that shipped with the chassis on one side.
Step 6
Repeat Step-2 through Step-3 on the other side of the chassis. Use all the screws to secure the rack mount brackets to
the chassis.
The chassis rack mount brackets must be installed first so that you can attach the cable management brackets
to the chassis rack mount brackets after the chassis is installed in the rack.
Note
Step 7
Gather the two cable management brackets and screws shipped with your chassis.
Attaching the Cable Management
shows the cable management brackets attached on the front of the Cisco ASR 1002-X Router.
Ensure that the cable management U feature device has the open end pointing upwards when you attach it to
the chassis
Note
Cisco ASR 1002-X Router Overview and Installation
15
Cisco ASR 1002-X Router Overview and Installation
Equipment Shelf or Tabletop Installation Procedure