Table 2-6
lists the power and the heat numbers for the Distributed Forwarding Cards (DFCs).
VS-F6K-PFC3C
Policy Feature Card 3C
1.90
79.80
99.75
340.65
107.26
366.29
VS-F6K-PFC3CXL
Policy Feature Card 3CXL
2.50
105.00
131.25
448.22
141.13
481.96
Table 2-5
Power Requirements and Heat Dissipation—Policy Feature Cards (PFCs)
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
Table 2-6
Power Requirements and Heat Dissipation—Distributed Forwarding Cards (DFCs)
Model Number/
Module Type
Module
Current (A)
Module
Power
(Watts)
AC
DC
AC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
DC-Input
Power
(Watts)
Heat Diss.
(BTU/HR)
WS-F6K-DFC
Distributed Forwarding Card
2.10
88.20
110.25
376.50
118.55
404.84
WS-F6K-DFC3A
Distributed Forwarding Card 3A
2.57
107.94
134.93
460.77
145.08
495.45
WS-F6K-DFC3B
Distributed Forwarding Card 3B
1.67
70.14
87.68
299.41
94.27
321.95
WS-F6K-DFC3BXL
Distributed Forwarding
Card 3BXL
2.38
99.96
124.95
426.70
134.35
458.82
WS-F6700-CFC
Centralized Forwarding Card
0.75
31.5
39.38
134.47
42.34
144.59