2-17
Cisco 12010, Cisco 12410, and Cisco 12810 Router Installation and Configuration Guide
OL-11496-01
Chapter 2 Preparing for Installation
Site Requirement Guidelines
You must terminate DC power cables using cable lugs at the power shelf
end.Ensure the lugs are dual-hole and that they fit over M6 terminal studs at
0.625-inch (15.88-mm) centers (for example, Panduit Part Number LCD8-14A-L
or equivalent).
shows the type of lug required for DC-input cable connections.
Figure 2-9
DC Power Cable Lug
shows a typical source DC power distribution scheme for a 2400 W
DC PDU.
Crimp area
25527
2.24
0.48
0.08
0.25
0.37
0.63
End View
Ø 0.267
2 holes
All measurements in inches