52
SVGm
Instruction Manual
Table 21 (Cont�) : Alarm messages�
Alarm messages
Selt-test failed
Description
The self-test system has detected a fault.
Corrective
action
Contact the
Technical Service
.
Temperature
Description
Power derating due to temperature reached 50%.
Corrective
action
Ambient temperature too high. Cooling system damaged. Clean fans and air inlet grid.
DSP failure
Description
DSP or software possible malfunction.
Corrective
action
It may happen during software update. Wait 5 minutes. Reset alarm. If it continues, contact Technical
service.
5V supply failure
Description
Power supply failure.
Corrective
action
Contact Technical service.
Internal comms error
Description
Failure in internal communications.
Corrective
action
Restart. Contact the
Technical Service
.
6�8�- WARNINGS
Note:
This screen is not visible on the
“slave”
devices.
When the device generates a warning, it will continue to operate, but the
symbol will be displayed
on the main screen.
On pressing the
key; if there are active warnings, the screen shown in
, will be dis-
played and the user will be asked for confirmation to continue with the static generator start-up pro-
cess.
Figure 48: Confirm screen�
This screen,
, shows the active warnings.