29
Instruction Manual
RECmax Lpd
Press the
PROG
key to save the selected sequence and exit the setup menu; when exiting, the screen
is displayed for a few seconds.
If you do not press any key for 5 s, the screen shown in
appears and the device opens the
Delay and Sensitivity
screen, without saving the changes made.
If
SRM
and
SRD
have been configured with the number 0 sequence, automatic reclos-
ing will be fully disabled. The
REC
symbol disappears from the display.
Default value:
MA 5
6�2�3�- RSTC: PARTIAL METER RESETTING
The partial reclosing meters are reset on this screen.
PROG
PROG
PROG
Press the
RESET
key to move between the different options:
NO
, the meters are not reset.
YES
, the meters are reset.
Press the
PROG
key to save the selected option and exit the setup menu; when exiting, the screen in
is displayed for a few seconds.
If you do not press any key for 5 s, the screen shown in
appears and the device opens the
Delay and Sensitivity
screen, without saving the changes made.
In this section only the partial meters are set to zero, i.e., those that separately accu-
mulate the no. of recloses caused by a circuit breaker trip (MA) or by an earth leakage
trip (DI). See
"6.2.6.- FACT: FACTORY CONFIGURATION”
to reset the total meter.
Default value
: NO
6�2�4�- POLT: CONFIGURATION OF TRIP OUTPUT
Configure the type of contact of the
TRIP
output on this screen.
PROG
PROG
PROG
Press the
RESET
key to move between the different options: