When the value on the screen is the desired value, press the
PROG
key to jump to the next program-
ming point.
If you do not press any key for 5 s, the screen shown in
appears and the device opens the
Delay and Sensitivity
screen, without saving the changes made.
Figure 15: Screen indicating that the programming menu has been exited�
Default value:
INS
6�1�2�- SENSITIVITY CURRENT, I
Δ
N
On this screen configure the current above which the earth leakage will be tripped,
I
Δ
N�
A
I n
PROG
Press the
RESET
key to modify the value. The possible values are:
30 mA, 0�1 A, 0�3 A, 0�5 A, 1A�
Earth leakage protection for people must be adjusted to 30 mA and automatically
means an instantaneous delay adjustment. Therefore, whenever
I
Δ
N
is configured
to 30 mA, the device will prevent any other adjustment of the delay.
Press the
PROG
key to save the modified values and exit the setup menu; when exiting, the screen in
is displayed for a few seconds.
Figure 16: Screen indicating that the data has been saved�
If no key is pressed for 5 s, the screen in
appears and the device exits the setup menu without
saving the changes made.
Default value:
30 mA