background image

INSTRUCTION MANUAL

(M202B01-03-20A)

RCCB with automatic reclosing device

REC  4    

Summary of Contents for REC 4

Page 1: ...INSTRUCTION MANUAL M202B01 03 20A RCCB with automatic reclosing device REC 4...

Page 2: ...2 REC4 Instruction Manual...

Page 3: ...he following should be taken into consideration Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit In particular handling with voltages appl...

Page 4: ...7 3 3 CONNECTION 8 3 3 1 CONNECTION DIAGRAM 2 POLE MODEL REC4 2P 8 3 3 2 CONNECTION DIAGRAM 4 POLE MODEL REC4 4P 9 4 OPERATION 10 4 1 DESCRIPTION 10 4 2 LEDs 11 4 3 START UP 12 4 3 1 AUTOMATIC MODE 12...

Page 5: ...ly for the purpose of illustration and may differ from the original device SYMBOLS Table 2 Symbols Symbol Description In compliance with the relevant European directive Device covered by European dire...

Page 6: ...reclosing mode is used for high sensitivity protection so that the device only recloses when the fault that caused tripping has disappeared The rest of the models imple ment the timed reclosing mode t...

Page 7: ...sulting from the use of non original products or accessories or those made by other manufacturers If you detect any operational faults in the device or in its protection system remove the device from...

Page 8: ...rmanent failure AUTO and REC LEDs are lit you must check the RCCB and the installation If the installation of the device is done with the RCCB in the OFF state when panel receives voltage the device w...

Page 9: ...ECTION DIAGRAM 4 POLE MODEL REC4 4P CARGA LOAD L3 N L1 L2 Figure 2 Connection diagram REC4 4P Three phase system CARGA LOAD F N Figure 3 Connection diagram REC4 4P Single phase system 9 Instruction Ma...

Page 10: ...most important pieces of device LEDs Protection cover TEST key Mode selection switch RCCB Control module Figure 4 Description of the REC4 2P LEDs Protection cover TEST key Mode selection switch RCCB C...

Page 11: ...There is no power to the REC4 ON OFF Automatic ON No rearm sequence has been initiated ON Slow flashing Automatic OFF Rearm sequence initiated Time delay of the rearm sequence if applica ble ON Fast...

Page 12: ...the RCCB cover 5 Put the mode selector switch in Automatic Mode ON Note The switch has an M2 hole where you can attach a seal or a padlock to block access to the RCCB and any other attempts at manual...

Page 13: ...disable the unit s automatic reclosing device Figure 8 The RCCB must be reclosed manually The AUTO and REC LEDs are off Figure 8 REC4 in manual mode with mode selector switch at OFF 4 4 2 AUTOMATIC T...

Page 14: ...Reclosures 1 2 3 Delay Restart Delay Restart Delay Restart 3 sec 10 sec 20 sec 20 sec 180 sec 60 sec The leakage current will be supervised by measuring the resistance downstream of the tripped RCCB 4...

Page 15: ...frequently Test sequence Figure 10 1 Press the TEST T key 2 Check that the RCCB jumps to OFF position TEST OFF Figure 10 RCCB Test Sequence In the event of a Test sequence failure contact the after sa...

Page 16: ...0 300 300 mA REC4 2P 63 300 REC4 4P 40 30 30 mA REC4 4P 63 30 REC4 4P 40 300 300 mA REC4 4P 63 300 Resistance to surges class A AC 250A 8 20 s class S 3000A 8 20 s Resistance to short circuits Inc 100...

Page 17: ...c Colour RAL 7035 Dimensions mm Figure 11 and Figure 12 Standard Residual current operated circuit breakers without integral overcurrent pro tection for household and similar uses RCCB s Part 1 Genera...

Page 18: ...81 91 5 35 5 101 55 87 5 45 76 Figure 12 REC4 4P dimensions 18 REC4 Instruction Manual...

Page 19: ...code or that surpasses the limits indicated in the technical and environmental features of this manual CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the instal...

Page 20: ...9 CE CERTIFICATE 20 REC4 Instruction Manual...

Page 21: ...21 Instruction Manual REC4...

Page 22: ...22 REC4 Instruction Manual...

Page 23: ...23 Instruction Manual REC4...

Page 24: ...CIRCUTOR SA Vial Sant Jordi s n 08232 Viladecavalls Barcelona Tel 34 93 745 29 00 Fax 34 93 745 29 14 www circutor es central circutor com...