If the
TELE REC 2
indicates a permanent failure (
AUTO
and
REC
LEDs are lit),
you must check the RCCB and the installation
If the installation of the unit is done with the RCCB in the OFF state, when pan-
el receives voltage the unit will not activate the automatic reclosing system for
safety reasons. The
AUTO
and
REC
LED turn on after a few seconds. A manual
reclosing of the system must be done on the panel with voltage.
3.5.- OUTPUTS:
REC 3C 2 poles and REC 3C 4 poles
In
we see the connection of the 2-pole changeover contacts on the
REC 3C 2 poles
and
REC 3C 4 poles
5
4
3
2
1
230 V 0,13 A
5
4
3
2
1
Figure 9: Connection of pole changeover contacts for the REC 3C 2 poles and REC 3C 4 poles�
Pole changeover contact terminals
Table 4:Pole changeover contact terminals for the 4-pole and 4-poles REC 3C
RCCB Estatus
Signalling RCCB Status
OFF
Terminals
3-5
closed contact.
Terminals
3-4
open contact.
ON
Terminals
3-5
open contact.
Terminals
3-4
closed contact.
Model
RCCB Status
Signalling Locked Status
3 reclosures
OFF/ON
No reclosures
≤
3
Terminals
3-1
closed contact.
Terminals
3-2
open contact.
OFF
No reclosures
>
3
Terminals
3-1
open contact.
Terminals
3-2
closed contact.
16
Instruction Manual
REC 3 - REC 3C
Summary of Contents for P26121
Page 1: ...INSTRUCTION MANUAL RCCB with automatic reclosing device REC 3 REC 3C M98252001 03 18A...
Page 2: ...2 Instruction Manual REC 3 REC 3C...
Page 26: ...10 CE CERTIFICATE 26 Instruction Manual REC 3 REC 3C...
Page 27: ...27 Instruction Manual REC 3 REC 3C...
Page 28: ...28 Instruction Manual REC 3 REC 3C...