Transients
Transients are detected by checking that the difference between one sample and the next does
not exceed the maximum nominal slope value multiplied by the distortion level coefficient se
-
lected by the user (“
).
In this case 128 samples are checked per cycle.
The maximum nominal slope value is the maximum tangent value calculated using a nominal
value selected by the user. By definition, in a sine wave this maximum slope is given by the zero
crossing, therefore the maximum slope is calculated as the value of the sine wave between
sample point 0 (zero crossing) and point 1 (first sample).
Transients are checked and saved phase by phase. The 3 voltage phases are checked sepa-
rately and when a transient is detected it saves the 15 wave shape cycles of the variable that
caused it.
Example:
shows the disturbances detected when configuring a distortion coefficient of
5�0
Figure 29:
Transients detected with a distortion coefficient of 5.0.
shows the disturbances detected when configuring a distortion coefficient of
90�0