4�2�1�- QUALITY PARAMETERS
Power quality control requires defining the TRMS of the voltage level, subsequently used by
the analyzer to record events. According to Standard EN-61000-4-30, the RMS value must be
calculated for all the AC magnitudes or each cycle and refresh every ½ cycle. If the RMS value
exceeds certain programmed thresholds, this is understood as an
event�
The device detects quality parameters such as overvoltages, gaps, voltage outages and tran-
sients.
shows an example of these events.
Figure 28:Example of quality events�
Overvoltage
An overvoltage event is shown in the time interval
t0
. The duration of the event
is the time that the signal stays above the configured threshold value (“
). In this example it is 110% of the rated voltage plus the time the signal takes to fall
below the configured value, including a hysteresis of 2%.
Voltage gap
In the time intervals
t1
and
t3
of
there are two voltage gaps. The duration of the event
is the time that the signal stays below the configured threshold value (
). In this
example it is 90% of the rated voltage.
Voltage outage
An outage or disruption event is shown in the time interval
t2
. The duration of the
event is the time that the signal stays below the configured threshold value (“
). In this example it is 10% of the rated voltage plus the time the signal takes to
rise above the configured value, including a hysteresis of 2%.