Configuration values
Table 25: Configuration values: Relay mode�
Relay mode
Possible values
oFF
, relay output 1 is disabled.
rEn
, remote control output.
ALr
, alarm output.
To validate the data, press the
key.
Use the
and
keys to browse the configuration screens of the menu.
5�4�2�- RELAY PULSE DURATION
The alarm relay can behave in 2 different ways:
1�-
The relay is activated when the alarm is triggered and is deactivated when the alarm is de-
activated.
2�-
The relay is activated when the alarm is triggered and is deactivated after a programmed
period of time, even though the alarm condition has not been cancelled.
This screen is used to configure the programmed time, i.e., the relay pulse duration.
To make the relay operate in mode
no� 1
, program the value to
0
.
tinE
ñ
-
000.0
S
Use the
, key to modify the value of the flashing digit
When the desired value is shown on the screen, press the
key to skip the digit.
Configuration values
Table 26: Configuration values: Relay pulse duration�
Relay pulse duration
Minimum value
000.0 s
Maximum value
999.9 s
To validate the data, press the
key.
Use the
and
keys to browse the configuration screens of the menu.
5�4�3�- ALARM PARAMETER
This screen is used to configure the parameter that will be used to activate the alarm.
itEn
ñ
-
U--H
-