6�1�4�- PRIMARY CURRENT
This screen is used to configure the value of the primary current.
inpt
Ct 1
0005
.
.
A
k
>3s
inpt
Ct 1
0005
.
.
A
k
With a long keystroke (>3s), press
to access the value's configuration.
Use the key
to modify the value of the flashing digit.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
When you reach the last digit and press the
key, you select the position of the decimal point. Use
the key
to modify the decimal point.
Minimum configuration value:
0.001 kA
Maximum configuration value:
20 kA
With a long keystroke, press
to validate the data.
Use the keys
and
to browse through the menu screens.
6�1�5�- SECONDARY CURRENT
This screen is used to configure the value of the secondary current.
inpt
Ct 2
0005
.
A
>3s
inpt
Ct 2
0005
.
A
With a long keystroke (>3s), press
to access the value's configuration.
Use the key
to modify the value of the flashing digit.
When the desired value is shown on the screen, press the
and
keys to skip the digit.
Minimum configuration value:
1 A
Maximum configuration value:
6 A
With a long keystroke, press
to validate the data.
Use the keys
and
to browse through the menu screens.