Table 112: Modbus memory map: Manual programming of outputs, expansion modules (Table 3)�
Manual programming of transistor digital outputs: Slot 2
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status
C810
C824
C838
C84C
C874
C874
C888
C89C
Value
C811
C825
C839
C84D
C875
C875
C889
C89D
Note:
The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
Table 113: Modbus memory map: Manual programming of outputs, expansion modules (Table 4)�
Manual programming of transistor digital outputs: Slot 3
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status
CBF8
CC0C
CC20
CC34
CC48
CC5C
CC70
CC84
Value
CBF9
CC0d
CC21
CC35
CC49
CC5D
CC71
CC85
Note:
The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
Table 114: Modbus memory map: Manual programming of outputs, expansion modules (Table 5)�
Manual programming of transistor digital outputs: Slot 4
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status
CFE0
CFF4
D008
D01C
D030
D044
D058
D06C
Value
CFE1
CFF5
D009
D01D
D031
D045
D059
D06D
Note:
The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
7�3�4�3�- Programming the digital inputs
The following functions are implemented for these variables:
Function 0x04
: reading registers.
Function 0x10
: Writing multiple registers.
Table 115:Modbus memory map: Digital inputs, expansion modules (Table 1)�
Configuration of Digital Inputs
Configuration variable
Valid data window
Default value
Mode
0
: Logic state
> 0
:Impulses
(83)
0
Logic (Logic state)
0
: positive
1
: Negative
0
Input name (impulses)
(84)
8
characters
“INPUT”
Units (Impulses)
(84)
6
characters
-
No. of decimals (Impulses)
0
to
5
0
(83)
When programming a value of more than 1, program the impulse operating mode and energy meter factor for
this mode simultaneously.
(84)
the characters must be sent in hexadecimal.
286
CVM-A1000 - CVM-A1500
Instruction Manual
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...