POWER FACTOR REGULATOR   Computer 

max

 

6f / 

max

 

12f

 

 

The 

Computer 

max

 

6f

max

 

12f

 

PF regulators measure cos

 in a supply system and control the connection and disconnection of capacitors 

to obtain a target programmed value. 

 

 

 

 

 

This  manual  is  an  easy  guide  for  the  use  and  operation  of  the 

Computer 

max 

6f

/

max

 

12f

.    For  more  information,  the  complete 

manual  can  be  downloaded  from  the  web  site  of  Circutor:  

www.circutor.es

 

 

 

 

Any  manipulation  or  use  of  the  equipment  out  of  the  conditions 
specified  by  the  manufacturer  may  put  in  risk  the  user  safety

.  Before 

any maintenance operation the equipment must be disconnected from power 
supply. In case of miss operation or protection fault the equipment must be 
disconnected  from  supply  and  remain  out  of  service  ensuring  against  any 
accidental reconnection.  

 

1.-  Regulator Connection 

 

 

For  proper  operation  it’s  necessary  to  install  a  current  transformer,  CT 
(normally  In  /  5  A),  which  primary  must  be  sized  according  to  the 
maximum expected load current in the installation. 
The  regulator  supply  (C-D  terminals)  must  be  taken  between  two 
phases and the CT should be located in the third phase. See technical 
characteristics for cable sizes and required protections. 
Must use an switch or automatic switch for supply the regulator 

 

 

The  current  transformer  ,  CT, 
must  be  located  so  that  it 
measures  the  whole  load  current 
plus the correction capacitors 

 

   

2.-  Technical Characteristics 

Supply and V measurement input 

terminals (C-D) 

480,400, 230 or 110 VAC +15% -10% ;  45-65 Hz , (see label) 

Connect preferably to phases  L2-L3 

Supply cables size and protection  Cross section 1,5mm

2

 ; 0,5 to 2A  Fuses  gl  type    

Current  measurement circuit 

Current transformer (CT) ,  In /5 , Place preferably in phase  L1 

Minimum cabling cross section  2,5mm

Current measurement margin 

0,05  to 5 A  (maximum ov20%) 

Accuracy of measurements 

Voltage and current :1%;   cos

  : 2% 

  1 dígit 

Max. Power consumptions 

110V: 7,3 VA    230V: 7,5 VA    400V: 5 VA    480V: 7 VA 

Display 

1 line x 3 digits x 7se 20 icons 

Output Contacts 

MOS static output. Max 24V, 0.15A 

Alarm Output  

Last output automatically set as alarm output , if not in use 

Compliant to the following 
Standards 

EN 61010,  EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-
1, EN 50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8, EN 

61000-4-5, EN 61000-4-11 , UL 94 

Safety / Insulation  

Category III ,  Class II,  According to  EN 61010-1,  

Environment limit conditions 

Temperature limits: -20ºC a +60ºC;  Relative Humidity 95% 

(without condensation). Max. Altitude: 2000m 

Protection degree 

IP40 (panel mounted)

 

IP30 (regulator box) , According to EN-60529 

Control system 

FCP (Minimum number of operations) 
Total (Connection/Disconnection of all stages needed) 

 
 
 
 

 

3.-  Four Quadrants Operation 

The 

Computer 

max 

6f

/

max

 

12f 

regulators operate in 4 quadrants (suitable 

for  imported  or  exported  active  power).  For  exported  power,  a  negative 
symbol  is  displayed  in  the  cos

  indication.  Check  phase  connection  and 

setup if there is no exported energy and the indication is not correct (see 4.3, 
SET-UP - phase) 
 

 

 

 

Display / Teclado 

 

 Standard mode: Displays cos

   

 

cos

 Indication / setting 

 

 C/K setting. See paragraph 6 

 

 Program setting. See 4.2 

 

 Delay time setting for switching on/off operations 

 

Nr of steps setting 

 

Setting CT phase and polarity  connection 

 

- Cursor keys (when in setting mode) 
- Manual ON / OFF  (push during more than 1s when in RUN mode) 
- Push both to see the Nr of connected steps 

 

SETUP KEY: Push during more than 1s to enter SETUP mode 

 

Lagging current indication (Inductive load) 

11

 

Leading current indication (Capacitive load) 

 