4.-  Setup and measurements  

 

To enter the SETUP mode, press the setup key (9), for more than 1s. If all the capacitors are disconnected, the access in immediate, otherwise a disconnection sequence 
starts and then accesses to setup menu. In the SETUP mode, if no key is pressed for 3 minutes, the equipment exits such mode and returns to normal operation mode. 

 

Key to access the SETUP mode:

 

-  Long push to enter and exit SETUP mode.  Also DELETE max values when 

in the measuring mode 

-  Short push: to change from display mode to edit mode and vice versa. 

If no key is pushed during more than 3 minutes, the regulator exits the SETUP 
mode without changing the setup. 

:

   

Symbol showing which parameter is being displayed or edited. 

 

- In the display mode:  Cursors to select an option.   

  

points to the option 

- In edit mode:  Change a parameter value 

Display SETUP Parameters 

Edit SETUP parameters 

Description 

 

MENU OPTIONS 

 

Target cos 

  (def=1) 

Reactive I of 1

st

 step, 

C/K adjustment 
Range:    0.02 – 1.00 
See paragraph 6 
Program setting 
Depends on the kvar 
relationship between 
successive steps.  
See paragraph  4.2   

Delay for successive 
steps  (2 -99 cycles) .  

 
Selection of Nr of 
outputs , max 6 or 12 
depending on type 
 
CT connection .  See 
paragraph  4.3.  The 
display shows  T1, T2, 
T3, T4, T5 or T6. 
Accept the option 
giving cos

  between 

0.7 Ind  and 0.98 Cap 
 
CT primary current 
setting. See 
paragraph 4.4 
 

 

 

 

4.1.- RUN & Measuring mode 

In  normal  operation  mode  (RUN  mode)  the  regulator  display  may  show  different 
parameters (V, I, cos

, etc.) The displayed parameter is pointed by the sign   . 

By  default  the  regulator  displays  the  cos

,  but  pushing  the  keys 

  the 

following parameters can be explored: Current (I), Current harmonics (THD), Mains 
Voltage (V),  Maximum current (I  MAX)  y  Maximum  voltage (V  MAX).  If both  keys 
are pushed simultaneously the regulator displays the Nr of connected steps.  

A long push of 

 key in maximum values screen causes de deletion of recorded 

max  values,  in  other  parameters  visualization  screens  we  will  go  to  SETUP 
screens. 

 

4.2.- Program selection 

This  setting  depends  on  the  kvar  ratio  between  the  different  capacitor  steps.  For 
instance if the bank is 10+20+20+20 kvar the program is 1:2:2:2, so the option 122 
must be selected. The program P00 of simulation allows to see on screen the steps 
that it would connect without managing to do it. 

Display 

Program 

Display 

Program 

Display 

Program 

P00 

Simulation 

111 

1:1:1:1 

T11 

1:1:1:1 (Total) 

 

 

122 

1:2:2:2 

T22 

1:2:2:2 (Total) 

 

 

124 

1:2:4:4 

T24 

1:2:4:4 (Total) 

 

 

248 

1:2:4:8 

T48 

1:2:4:8 (Total) 

 

 

112 

1:1:2:2 

T12 

1:1:2:2 (Total) 

 

4.3.- Selecting the CT connection phase 

Choose  among  the  options  in  the  table  depending  on  CT  connection  and  the 
phases where V is measured. In normal installations (no exported energy) choose 
the option for which the displayed cos

  is between 0.7 Ind and 0.98 Cap. 

Display 

V-I phase shift at 

cos

=1 

Measuring phases 

for V 

Phase where TC is 

connected

 

T1 

30º 

L3-L2 

L3 

T2 

270º 

L3-L2 

L1 

T3 

150º 

L3-L2 

L2 

T4 

210º 

L3-L2 

L3 (CT reversed) 

T5 

90º 

L3-L2 

L1 (CT reversed) 

T6 

330º 

L3-L2 

L2 (CT reversed) 

 

4.4.- Selecting the rated primary current of CT 

 

If the LED is blinking indicates that we are in SETUP mode and 

adjusting primary CT current. When in RUN mode or when 

Iprimary

 is displayed, 

the LED indicates whether the displayed current has a scale factor x1 (LED  OFF) 
or x10 (LED ON) 

5.-  Error Codes  

ERR  CODE 

DISPLAY 

DESCRIPCIÓN 

ACTUACIÓN 

000 

Alll zeros 

Load current below measuring threshold or 

CT not connected 

Forces all the 

outputs OFF 

E.02

 

cos 

  and  E.02 

alternate blinking 

Overcompensation. The regulador  is asking to 
disconnect Cs and they are all  disconnected 

NO ACTION 

E.03

 

cos 

   and  E.03 

alternate blinking 

Sub-compensation. The regulator is asking for more 
Cs and they are all connected 

NO ACTION 

E.04

 

cos 

   and  E.04 

alternate blinking 

Over current. The current is + 20%. Above primary 
rated current 

NO ACTION 

E.05

 

cos 

   and  E.05 

alternate blinking 

Overvoltage. Voltage is +15%. Above rated voltage 

NO ACTION 

 

6.-   C/K  table depending on initial cos

 , desired cos

 and CT ratio 

 CT Ratio 

Lower step reactive power (kvar) at  400V  

  

C/K calculation: 

If  

It

  is the primary rated current of the CT and  

Ic

 the rated current of the lower capacitor step, 

the C/K must be set according to the 
calculations shown below: 
         
Example  :  CT current ratio  = 500/5 
Lower step power: 60 kvar at  400V 

A

7

,

86

400

73

,

1

000

.

60

I

      

;

100

5

500

K

C

867

,

0

100

7

,

86

K

Ic

K

/

C

 

 
 

It

K

5

 

 

V

.

3

Q

I

C

 
 

C K

Ic
K

/

 

 

CT  

2.5 

5,00 

7.5  10,0  12,5  15,0  20,0  25,0  30,0  37,5  40,0  50,0  60,0  75,0  80,0 

150/5 

0,12  0,24  0,36  0,48  0,60  0,72  0,96 

  

  

  

  

  

  

  

  

200/5 

0,09  0,18  0,27  0,36  0,45  0,54  0,72  0,90 

  

  

  

  

  

  

  

250/5 

0,07  0,14  0,22  0,29  0,36  0,43  0,58  0,72  0,87 

  

  

  

  

  

  

300/5 

0,06  0,12  0,18  0,24  0,30  0,36  0,48  0,60  0,72  0,90  0,96 

  

  

  

  

400/5 

0,05  0,09  0,14  0,18  0,23  0,24  0,36  0,48  0,58  0,67  0,72  0,87 

  

  

  

500/5 

  

0,07  0,11  0,14  0,18  0,22  0,29  0,36  0,45  0,54  0,54  0,72  0,87 

  

  

600/5 

  

0,06  0,09  0,12  0,15  0,18  0,24  0,30  0,36  0,45  0,48  0,60  0,72  0,90  0,96 

800/5 

  

  

0,07  0,09  0,11  0,14  0,18  0,23  0,27  0,33  0,36  0,45  0,54  0,68  0,72 

1000/5 

  

  

0,05  0,07  0,09  0,11  0,14  0,18  0,22  0,27  0,29  0,36  0,43  0,54  0,57 

1500/5 

  

  

  

0,05  0,06  0,07  0,10  0,12  0,14  0,18  0,19  0,24  0,29  0,36  0,38 

2000/5 

  

  

  

  

  

0,05  0,07  0,09  0,11  0,13  0,14  0,18  0,22  0,27  0,28 

2500/5 

  

  

  

  

  

  

0,06  0,07  0,09  0,10  0,12  0,14  0,17  0,22  0,23 

3000/5 

  

  

  

  

  

  

0,05  0,06  0,07  0,09  0,10  0,12  0,14  0,18  0,19 

4000/5 

  

  

  

  

  

  

  

  

0,05  0,06  0,07  0,09  0,11  0,14  0,14 

For different voltages (V) of 400V, table result must be multiply for 400/V, or calculate C/K parameter using the expressions. 

7.-  Technical Service 

For any inquiry about the regulator operation or in case of malfunction, see 
detailed manual at www.circutor.es or contact with technical service.        
 
 

 
   

       