8.- TECHNICAL FEATURES
Power supply
Mode
Self-powered
Voltage Measurement
Connection
Single-phase
Reference voltages
230 V ~
Frequency
CEM-C12
50 / 60 Hz
CEM-C12-MID
50 Hz
Power consumption
≤ 10 VA, ≤ 0.4 Wh
Current measurement
Current
0.25 ... 5 A
Maximum current (Imax)
100 A
Starting current
0.004 Ib
Accuracy
Accuracy
CEM-C12
Class 1 (IEC 62053-21)
CEM-C12-MID
Class B (EN50470)
RS-485 Communications
Bus
RS-485
Protocol
Modbus RTU
Baud rate
9600 - 19200 - 38400
User interface
Display
LCD
Maximum counter value
99999.9 kWh
Keys
1 key
LED (kWh)
1000 imp/kWh ( width: 90 ms)
Environmental features
Operating temperature
CEM-C12
-20ºC... +65ºC
CEM-C12-MID
-25ºC... +55ºC
Relative humidity (maximum value)
95%
Average humidity value of year
75%
Mechanical features
Dimensions ( Figure 12)
90 x 18 x 72 mm
Weight
0.10 kg
Enclosure
ABS, PC alloy material
Protection degree
IP 51 (indoor)
Connections
RS-485 (B-, S, A+)
≤ 1.5 mm
2
0.4 Nm
Flat, PH2
Neutral (N)
≤ 1.5 mm
2
0.4 Nm
Flat, PH2
Measure (L, LOAD)
≤ 22 mm
2
≤ 3 Nm
Flat, PZ2
Standards
Electrical energy metering equipment (AC)� Particular requirements� Part 21: Static
active energy meters (classes 1 and 2)
IEC 62053-21
21
Instruction Manual
CEM-C12
Summary of Contents for CEM-C12
Page 1: ...INSTRUCTION MANUAL M336B01 03 21A Multifunctional Energy Meter CEM C12 CEM C12 MID...
Page 2: ...2 CEM C12 Instruction Manual...
Page 24: ...11 CE CERTIFICATE 24 CEM C12 Instruction Manual...
Page 25: ...25 Instruction Manual CEM C12...
Page 26: ...26 CEM C12 Instruction Manual...
Page 27: ...27 Instruction Manual CEM C12...