7.- RS-485 COMMUNICATIONS
The
CEM-C12
has one RS-485 communications port to view the measurement data and configure the
devices. The visualization and configuration can also be done through the
CIRCUTOR PowerStudio
software.
Note:
Default values of RS-485 communication:
No. of peripheral 1, 9600 bps, No parity, 8 data bits
and 1 stop bit.
7�1�- MODBUS PROTOCOL
In the Modbus protocol, the
CEM-C12
device uses the RTU (Remote Terminal Unit) mode.
The Modbus functions implemented in the device are as follows:
Function 0x03
: Reading integer registers
Function 0x10
: Writing multiple registers
7�1�1� READING EXAMPLE: Function 0x03�
Question:
Voltage value
Address
Function
Initial
register
No� of
registers
CRC
01
03
0000
0002
C40B
Address: 01
, Peripheral number: 1 in decimals.
Function: 03
, Read function.
Initial Register: 0000
, register on which the reading will start. (Modbus address).
No of registers: 0002
, number of registers read.
CRC: C40B
, CRC Character.
Response:
Address
Function
No of Bytes
Register
no 1
Register
no 2
CRC
01
03
02
0000
091F
359A
Address: 01
, Responding peripheral number: 10 in decimals.
Function: 03
, Read function.
No� of bytes: 02
, No. of bytes received.
Register: 091F
, value of the voltage :0000091F : 2335 → 233.5V
CRC: 359A
, CRC Character.
7�1�2� WRITING EXAMPLE: Function 0x10�
Question:
Modify the Modbus baud rate to 9600 bps
Address
Function
Initial
Register
No of
Registers
No of Bytes
Value
CRC
01
10
0064
0001
02
0004
xxxx
18
CEM-C12
Instruction Manual
Summary of Contents for CEM-C12
Page 1: ...INSTRUCTION MANUAL M336B01 03 21A Multifunctional Energy Meter CEM C12 CEM C12 MID...
Page 2: ...2 CEM C12 Instruction Manual...
Page 24: ...11 CE CERTIFICATE 24 CEM C12 Instruction Manual...
Page 25: ...25 Instruction Manual CEM C12...
Page 26: ...26 CEM C12 Instruction Manual...
Page 27: ...27 Instruction Manual CEM C12...