Circutor CDP series Application Notes Download Page 10

                                                                                                                                  

 CDP

 

10                                                                                 

Application notes

 

The most important inverter parameters that have to be configured in the 

CDP

 are 

(

Table 4

): 

Table 4: Parameters to be configured in the CDP

.

 

Parameter 

Description 

Inverter type 

Inverter model. In this case select:  

DELTA

 

Inverter power 

Total power to be controlled by the CDP. 

Number of inverters 

Number of inverters to control. 

Phase 

Architecture of the inverter connections 

 

 

Consult the manual for more information on how to configure 
the CDP.

 

 
When working with several three-phase inverters in cascade, the sum of the 
power of all the inverters must be programmed in the 

Inverter Power 

variable in 

the 

CDP

 so that the same regulation percentage is sent to each one. 

 
When working with single-phase inverters in three-phase installations, the total 
power of all the inverters must be programmed by selecting the "

three single 

phases

" option in the "

Phase

" variable, and then entering the number of sets of 

three single-phase inverters in the installation in the "

Number of inverters

variable.  
 

Example

: If there are six 2 kW single-phase inverters (two on the L1 phase, two 

on the L2 phase and two on the L3 phase) the following configuration should be 
entered: 

 

Inverter power:  12000 W

 

 

Number of inverters: 2 

 

Phase: three single phases 

 

However, if there are three 2 kW single-phase inverters (one inverter per phase) 
the following configuration should be entered: 

 

Inverter power: 

6000 W 

 

Number of inverters

: 1 

 

Phase:

 three single phases 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for CDP series

Page 1: ...Connection and configuration of a CDP with DELTA RPI inverters APPLICATION NOTES M028E0901 03 15A...

Page 2: ...CDP 2 Application notes...

Page 3: ...lead to the risk of fire Carefully read the manual prior to connecting the unit Follow all installation and maintenance instructions throughout the unit s working life Pay special attention to the in...

Page 4: ...8A 8KW INVERTER 6 2 1 COMMUNICATION CABLE 6 2 1 1 CONNECTION OF ONE INVERTER 7 2 1 2 CONNECTION OF SEVERAL INVERTERS 7 2 2 INVERTER COMMUNICATION CONFIGURATION 8 3 CDP CONFIGURATION 9 4 COMMUNICATIONS...

Page 5: ...5 LOG OF REVISIONS Table 1 Log of revisions Date Revision Description 08 15 M028E0901 03 15A Original version Note The images of the units are solely for the purpose of illustration and may differ fr...

Page 6: ...roduct should be consulted and each company is responsible for providing technical support An inverter from the PRI family of inverters will be used as a model in these application notes 2 DELTA PRI M...

Page 7: ...rter terminals 2 1 1 CONNECTION OF ONE INVERTER Figure 2 shows the connection between the CDP and a single inverter Figure 2 Connection between a CDP and one inverter 2 1 2 CONNECTION OF SEVERAL INVER...

Page 8: ...with the CDP The AC and DC sides of the inverter must be connected to the mains before it can turn on Consult the inverter manual if you have any doubts The configuration of the DELTA inverter paramet...

Page 9: ...r the Install settings menu must enter a password 5555 Consult the manual for more information on how to configure the parameters 3 CDP CONFIGURATION There is a configuration web site for the CDP wher...

Page 10: ...the CDP so that the same regulation percentage is sent to each one When working with single phase inverters in three phase installations the total power of all the inverters must be programmed by sel...

Page 11: ...means the CDP is not communicating with the inverter In this case check the communication cables and the inverter communication configuration Correct communication between the CDP and the inverters co...

Page 12: ...a 3000W inverter generating 1400W Now we program the CDP indicating that the inverter power is 6000W The CDP will send the inverter a new setpoint so it can change its MPPT and the inverter will redu...

Page 13: ...d if the unit has been improperly used or the storage installation and maintenance instructions listed in this manual have not been followed Improper usage is defined as any operating or storage condi...

Page 14: ...CIRCUTOR SA Vial Sant Jordi s n 08232 Viladecavalls Barcelona Tel 34 93 745 29 00 Fax 34 93 745 29 14 www circutor es central circutor es...

Reviews: