CIB UNIGAS - M039208CA
36
Checking the detection current
To measure the detection signal follow the diagram in Fig. 22 - Fig. 23.
If the signal is not in the advised range, check the electrical contacts, the cleaning of the combustion head, the position of the photore-
sistor and if necessary replace it.
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner’s main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel cock of the supply line
Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
Fig. 22
Fig. 23
Control box
Minimum current intensity with flame-
Minimum detection signal
Siemens LAL
6.5µA
Flame detector
Minimum detection signal
Krom Schroeder IFW15
1µA