C.I.B. UNIGAS - M039132CD
10
Low NOx burners Technical specifications
BURNER TYPE
NGX280
M-.TN...0.25
NGX280
M-.TN...0.32
NGX280
M-.TN...0.40
Output
min.- max. kW
93 - 190
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.- max. (Stm
3
/h)
9,8 - 20
Gas Pressure
min.- max. mbar
(Note2) - 360
Power supply
230V - 50Hz
Total power consumption
kW
0,55
Electric motor
kW
0,25
Protection
IP40
Approx. weight
kg
47
Valves size
/
Gas connection
1” / Rp1
1”
1/4
/ Rp 1
1/4
1”
1/2
/ Rp 1
1/2
Operation
Single-stage
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
BURNER TYPE
NGX280
M-.xx...0.25
NGX280
M-.xx...0.32
NGX280
M-.xx...0.40
Output
min.- max. kW
60 - 190
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.- max. (Stm
3
/h)
6,4 - 20
Gas pressure
min.- max. mbar
(Note2) - 360
Power supply
230V - 50Hz
Total power consumption
kW
0,55
Electric motor
kW
0,25
Protection
IP40
Approx. weight
kg
47
Valves size
/
Gas connection
1” / Rp1
1”
1/4
/ Rp 1
1/4
1”
1/2
/ Rp 1
1/2
Operation
Progressive - Fully modulating
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
BURNER TYPE
NGX350
M-.xx...0.25
NGX350
M-.xx...0.32
NGX350
M-.xx...0.40
Output
min.- max. kW
65 - 260
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.- max. min.-
max.(Stm
3
/h)
7 - 27.5
Gas pressure
min.- max. mbar
(Note2) - 360
Power supply
230V - 50Hz
Total power consumption
kW
0,67
Electric motor
kW
0,37
Protection
IP40
Approx. weight
kg
47
Valves size
/
Gas connection
1” / Rp1
1”
1/4
/ Rp 1
1/4
1”
1/2
/ Rp 1
1/2
Operation
Progressive - Fully modulating
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
Summary of Contents for IDEA NG280
Page 45: ...C I B UNIGAS M039132CD 45...