8 - LOCATION & INSTALLATION
You must leave space for access to the front and to the right of the unit for maintenance and installation operations.
For free air intake, there must be at least 500 mm above the unit.
1000 mm
1000 mm
500 mm
Under no circumstances should these vertical units be installed in an atmosphere that is:
-
Explosive,
-
Flammable,
-
Corrosive, or dusty.
Once at the place of installation, remove the wooden blocks.
-
Different configuration options are possible:
•
The unit can be placed directly on the floor. In this case:
The unit must be placed on a flat, smooth surface which is as level as possible (ratio of approx. one to one thousand). The cabinet
frame must rest fully on its contact surface. The unit need not be anchored to the floor if it is operated under normal conditions.
• Or on one of the following bases:
Support base, cased base with grids, cased base with damper.
(See the technical characteristics for these options in paragraph 12.2).
It should be placed on a floor that is as level as possible.
Each base comes with feet, which allow the height to be adjusted (in the event of a raised floor) and the base to be levelled before
placing the unit on top.
Before placing the vertical unit on top, an adhesive seal (supplied with the option) is to be placed on the aluminium casing frame
to ensure its tightness.
The cabinet can also come with a plenum with grids or a free-cooling plenum.
(See the technical specifications for these options in paragraph 12.2)
Before placing the plenum on the vertical unit, apply the adhesive seal (supplied with the option) to its tightness.
For practical reasons, when the CW 115 model unit is in its final position, the
horizontal gussets (with round stamped holes), located at the bottom of the unit, can be removed (see photo).
Horizontal gussets
EN-7