11.2.9 -
BACNET IP (OR BACNET MSTP) gateway
This is incorporated in the electrics box.
The gateway is used to translate the main information available in MODBUS into BACNET IP (OR BACNET MSTP).
It is possible to connect 1 to 2 units to the BACNET IP (OR BACNET MSTP) gateway.
Please see the recommendations for routing cables in paragraph 11.3 and in the control manual (N09.41).
12 - COMMISSIONING
After making the necessary electrical and hydraulic connections, carry out the system start-up and check the following steps:
-
Check the tightness of the electrical connections
-
Check the hydraulic connections (direction of inlet/outlet connections)
-
Make sure the inside of the vertical unit is clean and free of any foreign bodies
-
Make sure the inside of the vertical unit is clean and free of any foreign bodies
-
Check the power supply voltage and heat protection calibration in accordance with the current ratings of the various components.
-
Check the height of the siphon
-
Vent the air out of the coils via the air vents
-
Check the circuits for any leaks; retighten the valve if necessary
-
To configure the setpoints, please refer to the control manual. "µAir Connect 2"
-
Depending on the solution chosen, the air flow may be:
-
adjusted based on the difference with the setpoint
-
fixed
(refer to the control manuals for the corresponding configurations)
-
If a master/slave control system is used, make sure each cabinet is interconnected by the connection cable,
-
Simulate a trip of the electrical components, controlled instruments and alarms.
-
Check the current of each.
Standard components:
• Temperature alarm
•
Air flow alarm
• Water leak alarm
• Fan motor assembly
Optional components:
• Temperature low limit alarm
• Outer contact servo control
• Electric heater
•
Humidifier
• Hot water valve
-
Check the cleanliness of the humidifier supply water (option),
-
After allowing the unit to run for a few hours, check the clogging level of the filter, especially in the case of an F7 filter.