98
Hexadecimal
b
it No.
Bit No.
decimal
Description
Type
0x82 to 0x9f reserved
0x100
256
Circuit 2 fault summary
Read-only
1 = Fault
0x101
257
Stage 1, circuit 2 fault
Read-only
1 = Fault
0x102
258
Stage 2, circuit 2 fault
Read-only
1 = Fault
0x103
259
Manual HP fault, circuit 2
Read-only
1 = Fault
0x104
260
HP fault, circuit 2 pressure sensor
Read-only
1 = Fault
0x105
261
Circuit 2 LP fault
Read-only
1 = Fault
0x106
262
Water frosting fault, circuit 2
Read-only
1 = Fault
0x107
263
Refrigerant frosting fault, circuit 2
Read-only
1 = Fault
0x108
264
Exchanger frosting fault, circuit 2
Read-only
1 = Fault
0x109
265
Discharge fault, stage 1, circuit 2
Read-only
1 = Fault
0x10a
266
Discharge fault, stage 2, circuit 2
Read-only
1 = Fault
0x10b
267
Defrosting fault, circuit 2
Read-only
1 = Fault
0x10c
268
Expansion valve fault, circuit 2
Read-only
1 = Fault
0x10d
269
Stepper motor fault, circuit 2 expansion valve
Read-only
1 = Fault
0x10e
270
Low superheat fault, circuit 2
Read-only
1 = Fault
0x10f
271
High superheat fault, circuit 2
Read-only
1 = Fault
0x110
272
VCM module fault, expansion valve 2
Read-only
1 = Fault
0x111
273
Exchanger outlet sensor fault, circuit 2
Read-only
1 = Fault
0x112
274
Exchanger freon sensor fault, circuit 2
Read-only
1 = Fault
0x113
275
Sensor fault, coil A, circuit 2
Read-only
1 = Fault
0x114
276
Sensor fault, coil B, circuit 2
Read-only
1 = Fault
0x115
277
Sensor fault, coil C, circuit 2
Read-only
1 = Fault
0x116
278
Sensor fault, coil D, circuit 2
Read-only
1 = Fault
0x117
279
Stage 1, circuit 2 discharge sensor fault
Read-only
1 = Fault
0x118
280
Stage 2, circuit 2 discharge sensor fault
Read-only
1 = Fault
0x119
281
Circuit 2 HP sensor fault
Read-only
1 = Fault
0x11a
282
Circuit 2 LP sensor fault
Read-only
1 = Fault
0x11b
283
Circuit 2 suction sensor fault
Read-only
1 = Fault
0x11c
284
Circuit 2 liquid sensor fault
Read-only
1 = Fault
0x11d
285
Circuit 2 exp. valve board link fault
Read-only
1 = Fault
0x11e
286
Link fault, additional board for reversible
Read-only
1 = Fault
0x11f to 0x13f reserved
0x140
320
Load shedding, stage 1, circuit 2
Read-only
1 = Load shedding
0x141
321
Load shedding, stage 2, circuit 2
Read-only
1 = Load shedding
Read (Functions 1 or 2) and write (Functions 5 or 15)
bit
0x200
512
On/Off
Read/Write
1 = On
0x201
513
Control set to setpoint 1 or 2
Read/Write
1 = Control set to setpoint 2
0x202
514
Heating or cooling operation
Read/Write
1 = Heating
0x203
515
Load shedding via Modbus, stage 1, circuit 1 (different from 0 x 140)
Read/Write
1 = Off
0x204
516
Load shedding via Modbus, stage 2, circuit 1
Read/Write
1 = Off
0x205
517
Load shedding via Modbus, stage 1, circuit 2
Read/Write
1 = Off
0x206
518
Load shedding via Modbus, stage 2, circuit 2
Read/Write
1 = Off
Read bit (Functions 1 or 2)
→ Available with versions 09.00 and higher
0x220
544
On/Off summary (1 = keypad on/off = 1 and all automaic
operation controls closed and no oil warm-up time and no
faults)
Read-only
0x221
545
1 = Cooling possible
Read-only
0x222
546
1 = Heating possible
Read-only
0x223
547
1 = 1 stage on
Read-only
0x224
548
1 = Maximum available power reached
Read-only
0x225
549
1 = A major fault preventing output has occurred
Read-only
0x226
550
1 = A reset fault has occurred but output is possible
Read-only
0x227
551
1 = A fault requiring servicing has occurred
Read-only
Summary of Contents for Magister 2 Series