9.7 - Input/Output directions
No.
Description
Setting
Display conditions
Access
level
Enumeration
By default
Adjust. params
850
Remote control input direction
0 : Normally open
1 : Normally closed
1 (NC)
2
851
Setpoint 1/Setpoint 2 input direction
0 : Normally open
1 : Normally closed
0 (NC)
P160 Setpoint 1/setpoint 2 = On/Off input
2
852
Fire detection input direction
0 : Normally open
1 : Normally closed
1 (NC)
P24 Fire detection = With
3
855
Changeover thermostat input direction
0: Open in heating
1: Closed in heating
1 (NC)
P28 = mixed coil and P162 = On/Off input
3
856
Intake filter pressure switch input direction
0 : Normally open
1 : Normally closed
1 (NC)
3
857
Exhaust filter pressure switch input direction
0 : Normally open
1 : Normally closed
1 (NC)
3
866
DX unit defrosting input direction
0 : Normally open
1 : Normally closed
1 (NC)
P28 Coil = Cooling direct expansion or
heating direct expansion or reversible direct
expansion
2
867
DX unit control input direction
0 : Normally open
1 : Normally closed
1 (NC)
P28 Coil = Cooling direct expansion or
heating direct expansion or reversible direct
expansion
2
872
Electric heater manual safety input direction
0 : Normally open
1 : Normally closed
1 (NC)
P32 Electric heater = 2 On/Off stages
3
882
Fault reporting output direction
0 : Normally open
1 : Normally closed
1 (NC)
2
885
AHU operating feedback output direction
0 : Normally open
1 : Normally closed
1 (NC)
2
886
DX unit control output direction
0: Open in heating
1: Closed in heating
1 (NC)
P28 Coil = reversible direct expansion
2
9.8 - Motors
No.
Description
Setting
Unit
Access
level
Enumeration
By default
Air intake FMA settings
1200
Min. speed percentage
0
%
3
1201
Max. speed percentage
100
%
3
1202
Acceleration ramp-up
100
s
3
1203
Deceleration ramp-down
100
s
3
Air intake FMA 1 information
1220
Calculated min. speed
rpm
1
1221
Calculated max. speed
rpm
1
1222
Speed requested
rpm
1
1223
Current speed
rpm
1
1224
Current consumed
A
1
1225
Power input
W
1
1226
Motor temperature
°C
1
1227
Operating counter
h
1
1230
Fault summary
0 : inactive
1 : active
1
1231
Communication state
0 : inactive
1 : active
1
1234
Warning summary
0 : inactive
1 : active
1
1235
Warning status
1
1238
Motor type
1
1239
Version number
1
Extraction FMA 1 settings
2200
Min. speed percentage
0
%
1
2201
Max. speed percentage
100
%
1
2202
Acceleration ramp-up
100
s
1
2203
Deceleration ramp-down
100
s
1
9 - PARAMETERS
FLOWAY ACCESS
EN-58