2.2.8 Error signals (fig. 2 )

If the 4 LEDs (fig. 2 ref. L, M, N, O), if the signal is enabled, indicates that the Divio comfort unit need maintenance. Select the 
stand-by programme, clean the air filter and then, when you switch the appliance back on, keep the MODE button (fig. 2 ref. Q) 
pressed for 5 seconds until normal functioning is restored.
If the AUTO and ERR LEDs (fig. 2 ref. L and P) both flash it indicates a room temperature probe fault. if the MIN and ERR LEDs 
(fig. 2 ref. M and P) both flash it indicates a fault on the water temperature probe located in the main battery, if both the NIGHT and 
ERR LEDs (fig. 2 ref. N and P) flash this indicates a fault in the secondary battery probe in the 4-pipe versions, if both the MAX 
and ERR LEDs (fig. 2 ref. 0 and P) flash this indicates a fault in the motor/HALL sensor. 
With the last signal the outputs of Divio function normally but the ventilation speed modulation function is inhibited and the fan 
functions at a fixed number of revs. 
If the MODE button is pressed the alarm signal is inhibited for 10 seconds and the temperature and operating settings can be made.  
The luminosity of the LEDs during normal functioning is deliberately reduced to increase your comfort at night time, but as soon 
as a button is pressed the maximum luminosity is restored for a period of 7 seconds from the last button-pressing.

2.2.9 Automatic functioning (fig. 2)

 

  

Selecting this operating mode, indicated when the relative LED lights up (fig. 2 ref. L). 
The temperature control and regulation are managed by a micro-processor system which automatically adapts the function of the 
appliance to the changing environmental conditions. In particular, the regulation of the ventilation speed is completely automatic, 
between a minimum value and a maximum value depending on the heating or cooling requirements in the room.
The cooling or heating is selected with the sum/win button (fig. 2 ref. H). If the automatic heating and automatic cooling setting is 
chosen, the command makes the adjustment based on the room temperature and is conditioned by the temperature of the water 
available inside the system.
Until the water temperature reaches a value which satisfies the request, the fan remains switched off, and the LED corresponding 
to the request (red heating fig. 2 ref. G, or blue cooling fig. 2 ref. A) flashes.
If the water temperature reaches an unsuitable value for the requested function (Example 1: heating function requested with room 
temperature of 20°C and water temperature below 15°C. Example 2: cooling function requested with room temperature of 20°C 
and water temperature above 25°C) after 10 minutes the control is blocked and only the err yellow LED (fig. 2 ref. P) lights up. The 
release is automatic after 45 minutes or manual when there is a passage from heating request to cooling request (or vice versa) 
or by pressing the MODE button  (fig. 2 ref. Q).

2.2.10

 

Silent functioning (fig. 2)  

Selecting this operating mode, indicated when the relative LED lights up (fig. 2 ref. M), the ventilation speed is limited to a lower value.
For the rest, the operation is the same as in automatic mode.

2.2.11 Night functioning (fig. 2)  

Selecting this operating mode, indicated when the relative LED lights up (fig. 2 ref. N), the set temperature is automatically adjusted 
as follows:
-  reduced by 1° C after one hour and a further degree after 2 hours in the heating function. 
-  Increased by1°C after one hour and a further degree after 2 hours in the cooling function.

2.2.12 Operation at maximum ventilation speed (fig. 2)  

With this operating mode, indicated when the LED lights up (fig. 2 ref. O), maximum power is obtained immediately both in heating 
and cooling.

2.2.13

 

Dirty filter signal (fig. 2)

When the 4 green LEDs on the control panel start flashing (fig. 2 ref. L, M, N, O), if the signal is enabled, this indicates that the air 
aspiration filter is dirty.
To clean the filter, consult the machine maintenance manual N12100.
Once the filters have been cleaned the signal must be reset by pressing the MODE button (fig. 2 ref. Q) for 5 seconds.

2.2.14  Deactivation 

To deactivate the appliance: 
-  Keep the MODE button (fig. 2 ref. L) pressed for 2 seconds until all the LEDs switch off. The command guarantees anti-freeze 
security even when in stand-by.

2.2.15 Shut-down for long periods

When switching off for long periods or holidays, proceed as follows:
-  Deactivate the appliance
-  Set the master switch to OFF.

The anti-freeze function is not active.

Summary of Contents for Divio Series

Page 1: ...DIVIO Installation Operation Commissioning Maintenance 10 2012 NA 12 103 A user ...

Page 2: ......

Page 3: ...2 2 2 Activation 4 2 2 3 MODE button 4 2 2 4 Manual heating cooling selection 4 2 2 5 Stand by 4 2 2 6 Selecting on board machine electronic control temperature 4 2 2 7 On board machine electronic control LED indications 4 2 2 8 Error signals 5 2 2 9 Automatic functioning 5 2 2 10 Silent functioning 5 2 2 11 Night functioning 5 2 2 12 Operation at maximum ventilation speed 5 2 2 13 Dirty filter si...

Page 4: ... create dangerous situations and the manufacturer will not be responsible for any damage caused 1 1 1 Compliance The CIAT Divio comfort units conform to European directives LVD EMC RoHS e RAEE 2006 95 EC 2004 108 EC 2002 95 EC and 2002 96 EC 1 2 Symbols The pictograms in the next chapter provide the necessary information for correct safe use of the machine in a rapid unmistakable way Index Paragra...

Page 5: ... LED bar setpoint settable from 16 to 28 C E Red LED 40 C extreme exceeded F Increase set temperature button G Red LED heating H Summer winter function button not available I Yellow LED Webserver supervision active only available if connected to a reversible heat pump or with the natural cooling option L Automatic function indicator M Silent function indicator N Night function indicator O Maximum ...

Page 6: ...ture and maximum maximum heating temperature fig 2 ref C and E Only set these values for short periods and then set the selection to an intermediate value The command is very precise set it to the desired value and wait until the command has made the adjustment To reduce the possibilities of temperature oscillations there is a neutral band of 2 C 1 C more and 1 C less than the selector setting 2 2...

Page 7: ...e the system Until the water temperature reaches a value which satisfies the request the fan remains switched off and the LED corresponding to the request red heating fig 2 ref G or blue cooling fig 2 ref A flashes If the water temperature reaches an unsuitable value for the requested function Example 1 heating function requested with room temperature of 20 C and water temperature below 15 C Examp...

Page 8: ...appropriate without prior notification CIAT service Habitat Tel 0 826 96 31 05 0 15 TTC min Siège social Avenue Jean Falconnier B P 14 01350 Culoz France Tel 33 0 4 79 42 42 42 Fax 33 0 4 79 42 42 10 info ciat fr www ciat com Compagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Ref 277424A ...

Reviews: