Due to floating no native floating point representation for the Modbus
communication protocol, IEEE754 representation has been integrated. As the
opposite, float handled as integer is also available (i.e. float X 10) depending on
setup.
Bus “port1” is proprietary and therefore reserved for internal purpose.
1.2. RJ45 socket details
Modbus Ethernet is intended to Modbus IP.
Used for wide area network communication type by external devices (building management
system tool or maintenance tool and so on…)
Cross pair wired cable shall be used for nominal configuration.
distance up to 100m without amplifier
Speed communication at 10 Mega baud not configurable
IPv4 address configurable for class address with DHCP NOT active for
Class A (0.xxx.xxx.xxx to 127.xxx.xxx.xxx)
Class B (128.0.xxx.xxx to 191. 255.xxx.xxx)
Class C (192.0.0.xxx to 223.255.255.xxx)
(IP address declared on the control unit needed to set up connection with external
device)
All requests are sent via Transfer Control Protocol on registered port 502 by default
but other port number may be set as calibrate value.
TCP/IP Modbus protocol is compatible with both Little/ Big Endian for data field (i.e.
either most significant byte is sent first or Least significant byte is sent first)
Unit identifier must be declared from 1 to 247 as slave product number setup (i.e.
station number)