![CIAT AquaCIAT LD Series User Manual Download Page 14](http://html1.mh-extra.com/html/ciat/aquaciat-ld-series/aquaciat-ld-series_user-manual_2606678014.webp)
ECG-UG-16-006
REVISION
DATE
PAGE
AquaCIAT LD/ILD
Modbus
Rev A
1/13/17
14 OF 20
Company private. Do not distribute outside of CIAT Corporation
Table
Item
Description
Media
Type
Address
(hex)
Format
RUNTIME
hr_fana1
Circuit A Fan #1 Hours
IR
338
(0152)h
IEEE Float
(32-bit)
RUNTIME
hr_fana2
Circuit A Fan #2 Hours
IR
340
(0154)h
IEEE Float
(32-bit)
RUNTIME
hr_fanb1
Circuit B Fan #1 Hours
IR
346
(015A)h
IEEE Float
(32-bit)
RUNTIME
st_fana1
Circuit A Fan #1 Starts
IR
354
(0162)h
IEEE Float
(32-bit)
RUNTIME
st_fana2
Circuit A Fan #2 Starts
IR
356
(0164)h
IEEE Float
(32-bit)
RUNTIME
st_fanb1
Circuit B Fan #1 Starts
IR
358
(0166)h
IEEE Float
(32-bit)
MODES
m_limit
Demand Limit Active
IR
370
(0172)h
Signed Integer
(32-bit)
MODES
m_heater
Electric Heat Active
IR
388
(0184)h
Signed Integer
(32-bit)
GENCONF
lead_cir
Cir Priority Sequence
IR
428
(01AC)h
Signed Integer
(32-bit)
GENCONF
off_on_d
Unit Off to On Delay
IR
434
(01B2)h
Signed Integer
(32-bit)
GENCONF
nh_limit
Night Capacity Limit
IR
436
(01B4)h
Signed Integer
(32-bit)
GENCONF
nh_start
Night Mode Start Hour
IR
438
(01B6)h
Signed Integer
(32-bit)
GENCONF
nh_end
Night Mode End Hour
IR
440
(01B8)h
Signed Integer
(32-bit)
HCCONFIG
both_sel
HSM Both Command Select
IR
448
(01C0)h
Signed Integer
(32-bit)
HCCONFIG
auto_sel
Auto Changeover Select
IR
450
(01C2)h
Signed Integer
(32-bit)
HCCONFIG
heat_th
Heating OAT Threshold
IR
454
(01C6)h
IEEE Float
(32-bit)
PUMPCONF pump_seq
Cooler Pumps Sequence
IR
456
(01C8)h
Signed Integer
(32-bit)
HCCONFIG
boil_th
Boiler OAT Threshold
IR
472
(01D8)h
IEEE Float
(32-bit)
HCCONFIG
ehs_th
Elec Stage OAT Threshold
IR
474
(01DA)h
IEEE Float
(32-bit)
FACTORY
unit_typ
Unit Type (HeatPump = 2)
IR
484
(01E4)h
Signed Integer
(32-bit)
FACTORY
unitsize
Unit Capacity Model
IR
486
(01E6)h
Signed Integer
(32-bit)
FACTORY
ehs_sel
Electrical Heater Select
IR
492
(01EC)h
Signed Integer
(32-bit)
FACTORY
boil_sel
Boiler Command Select
IR
494
(01EE)h
Signed Integer
(32-bit)
FACTORY
vsd_fan
Var Speed Fan Selection
IR
502
(01F6)h
Signed Integer
(32-bit)
FACTORY
dual_pmp
Factory Dual Water Pump
IR
508
(01FC)h
Signed Integer
(32-bit)
FACTORY
vsd_pump
Var Speed Water Pump Sel
IR
510 Signed Integer