99DA-SEI-EC01
Various settings are possible with this type of thermostat. Read the
installation manual carefully before installation. For proper operation,
please check the parameters below and adjust if necessary:
P01: 0 (system type)
P02: 1 (automatic change-over heat/cool)
C01: 17 (if water temp. lower than this value
→
cool) *
C02: 30 (if water temp. higher than this value
→
heat) *
C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) **
*
Install a water temperature sensor (SM ***) on a pipe where the
water supply can be measured and connect it to terminals 13 and 14.
** With the Comfort Line and the Major Line with ducting: the capacity (air
volume) depends on the resistance in the duct and the grilles. In
most cases, the maximum speed should be set between 5V and 8V.
*** Accessory, 99DA-SEI-SEN01
Explanations:
E/I = N/A *
RDC = Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor (change-over based on C01 and C02) **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit
*
The functions of these outputs can be changed with parameters C17,
C18 en C19. See for more information the installation manual.
**
Use a separate shielded cable (see for more information the
installation manual)
PE
3
8
5
14
A+
A-
5
5
12
10
PE
N
L
Major
Line
Melody 2
Coadis
Line
XB
XB
XB
Ph
N
Ph
6
Ph
Ph
6
C
PE
N
Ph
Ph
N
Ph
6
V1
V2
Ph
Ph
6
C
PE
N
Ph
XB
XB
XB
XB
Comfort
Line
+
-
NOTE: Check whether the unit is
suitable for 0-10V control of the
fan motor
POWER SUPPLY 230V~
2-PIPE FAN COIL UNITS CHANGE-OVER HEAT/COOL
WITH WATER SENSOR
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V
– on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3:
Minimum cable diameter 1,5 mm
2
(230V~)
4:
Use shielded cable for 0-10V signal cable of the fan motor
5:
For other connections/information, see the electrical wiring diagram of the relevant unit
Controlbox on the motor
Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump
Remark 4
18-05-2022