background image

L

N

3

4

5

6

7

8

9

10

11

12

13

14

15

16

L

CF

SA

E / I

RDC

GND

V HEAT

V COOL

V FAN

Ph

N

Ph

6

V1

V2

Ph

Ph

6

C

PE

N

Ph

N

L

JP1

TB

A1F / X2

TB

TB

XB

XB

XB

XB

SM

/

/

99DA-SEI-EC01

Various settings are possible with this type of thermostat. Read the 
installation manual carefully before installation. For proper operation, 
please check the parameters below and adjust if necessary:

P01: 0 (system type)
P02: 1 (automatic change-over heat/cool)
C01: 17 (if water temp. lower than this value 

cool) *

C02: 30 (if water temp. higher than this value 

heat) *

C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) **

*

Install a water temperature sensor (SM ***) on a pipe where the 
water supply can be measured and connect it to terminals 13 and 14.

**  With the Comfort Line and the Major Line with ducting: the capacity (air 

volume) depends on the resistance in the duct and the grilles. In 
most cases, the maximum speed should be set between 5V and 8V.

*** Accessory, 99DA-SEI-SEN01

Explanations:

E/I = N/A *
RDC = Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor (change-over based on C01 and C02) **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit

The functions of these outputs can be changed with parameters C17, 
C18 en C19. See for more information the installation manual.

**

Use a separate shielded cable (see for more information the 
installation manual)

PE

3

8

5

14

A+

A-

5

5

12

10

PE

N

L

Major

Line

Melody 2

Coadis

Line

XB

XB

XB

Ph

N

Ph

6

Ph

Ph

6

C

PE

N

Ph

Ph

N

Ph

6

V1

V2

Ph

Ph

6

C

PE

N

Ph

XB

XB

XB

XB

Comfort

Line

+

-

NOTE: Check whether the unit is 

suitable for 0-10V control of the 

fan motor

POWER SUPPLY 230V~

2-PIPE FAN COIL UNITS CHANGE-OVER HEAT/COOL
WITH WATER SENSOR 

APPLICATION

Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V 

– on/off

REMARKS

1:  All electrical connections must be made in accordance with the local regulations
2:  ---------- External cables (not supplied by CIAT)
3:

Minimum cable diameter 1,5 mm

2

(230V~)

4:

Use shielded cable for 0-10V signal cable of the fan motor

5:

For other connections/information, see the electrical wiring diagram of the relevant unit

Controlbox on the motor

Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump

Remark 4

18-05-2022

Reviews: