2.2 Configuring with slave HEE Mono Boxes only:

To configure the various slaves, the pLDPRO terminal must be removed from the master unit and connected to the slave units.

a) For the first slave:

 

● Power up the Slave HEE Mono Box

 

● To switch to configuration mode, simultaneously press the 

 and        keys for approx. 5 seconds; the page shown below 

will be displayed, with the cursor flashing in the top left corner:

Display address
Setting……………… : 32

I/O Board address  :  --

 

Press 

 

.

 

● Change the Display address setting from 32 to 00 by pressing 

, then press 

 

Terminal config

Press Enter 
To continue

 

● Switch off the Slave HEE Mono Box.

 

● Switch it back on again and then immediately press       and 

 for approx. 15 seconds.

pLan address : 1
UP:              increase
DOWN:       decrease
ENTER:      save & exit

 

● Change the pLan address to 2 by pressing 

, then press 

 

.  

If there are no other Slave HEE Mono Box(es), go to step c), otherwise go to step b) to configure the other Slave HEE 

Mono Box(es).
b) For the second Slave HEE Mono Box:

 

Connect the pLDPRO to the slave to be configured

 

● Power up the Slave HEE Mono Box concerned and immediately press on        and 

 for approx. 15 seconds

pLan address : 1
UP:            increase
DOWN:      decrease
ENTER:     save & exit

 

● Change the pLan address to 3 by pressing 

, then press 

 

.  

If you have other Slave HEE Mono Boxes to connect, simply adjust point b) by increasing the pLan address by 1 each time 

 

(e.g. 3rd slave: pLan address 4, 4th slave: pLan address 5, etc.).

 

 EN-7  

1-PH HEE BOX

Summary of Contents for 1-PH HEE BOX

Page 1: ...1 PH HEE BOX 05 2019 EN7515391 02 Control manual...

Page 2: ...1 PH HEE BOX EN 2...

Page 3: ...2 Addressing the pLAN 11 4 GENERAL DESCRIPTION OF THE SCREENS 11 4 1 Machine state 11 4 2 Setpoint menu 13 4 3 Machine parameters menu 13 4 4 Settings parameters menu 14 4 5 Read only parameters menu...

Page 4: ...The password protected configuration and operating parameters Device running times and time delays The connection with the pLAN network allows the program to use a terminal mounted on the front of the...

Page 5: ...port Modbus BACnet LON KNX On Off inputs 0 10 V analogue outputs 1 4 Description of the air handling units The unit can perform the following functions Ventilation Control monitoring reporting and reg...

Page 6: ...rox 5 seconds the page shown below will be displayed with the cursor flashing in the top left corner Terminal config Press Enter To continue To change the controller address I O Board address press tw...

Page 7: ...Switch it back on again and then immediately press and for approx 15 seconds pLan address 1 UP increase DOWN decrease ENTER save exit Change the pLan address to 2 by pressing then press If there are...

Page 8: ...hange the Display address setting from 00 to 32 by pressing then press Display address Changed Press and again for approx 5 seconds the page below will display Display address Setting 32 I O Board add...

Page 9: ...nd keys for approx 5 seconds the page shown below will be displayed with the cursor flashing in the top left corner Display address Setting 32 I O Board address Change the I O Board address by pressin...

Page 10: ...pear the pLAN may be unstable or more likely two components share the same address The number after Term indicates the address of the terminal used The example shows that the network is made up of 3 c...

Page 11: ...aster controller Address 2 Master controller Address 3 Master controller Address 31 4 GENERAL DESCRIPTION OF THE SCREENS 4 1 Machine state U 01 00 00 00 0 c Marche Puissance Totale U 01 Indicates the...

Page 12: ...your choice simply press The available menus are as follows 1 Setpoints 2 Machine status 4 Mach parameters 5 Adjust params 6 Reading parameter 8 Test mode 9 Timer programming 11 Communication 13 Alar...

Page 13: ...ers menu No Description Unit Min Max By default Increment Possible choices Visibility Levels Machine parameters menu P01 Unit size a 0 15 0 1 0 2 1 H4300 2 H4351 3 H4352 4 H4353 5 H4401 6 H4402 7 H440...

Page 14: ...Man 1 P119 Fan override time delay min 0 180 30 1 If fan override Man 1 P120 Air heater fan min speed 0 Air heater max speed 0 1 2 P121 Air heater fan max speed air heater min speed Calculated max sp...

Page 15: ...coil type mixed 1 P262 Fan operation feedback state C O Open Closed 1 P263 Antifreeze thermostat state C O Open Closed If frost protection thermostat present YES 1 P264 Remote on off command state C O...

Page 16: ...th and year of yearly time schedule Start time 00 00 End time in hours and minutes of yearly time schedule State Selection of the state during this period Off Comfort Eco Frost protection Note it is n...

Page 17: ...the key Confirm by pressing ENTER The unit is now in test mode The overrides are cancelled when the unit is set back to on Output Parameter Setting range Default value Access level Mask Air heater fa...

Page 18: ...c s ACCES NIVEAU 2 Nouveau mot de passe 0000 Non Re enter the new installer password Niveaux acc s ACCES NIVEAU 2 Retour au niveau 2 Non If access level 2 selected and access level 3 If yes back to ac...

Page 19: ...comfort setpoints either by Parameter P111 local or CMS or time schedule the last order received time schedule or parameter P111 is taken into account the on off input J4 DI6 only depending on the in...

Page 20: ...alve is closed COMFORT position the 0 10 V signal will depend on the difference between the regulated temperature value room and the setpoint Regulation will only start after a 30 second time delay on...

Page 21: ...a 30 second time delay on the fan operation feedback contact An integral action must be entered into the parameters 0 100 P 135 Valve ctrl Cooling operation Cold Proportional Band P150 or P151 Cooling...

Page 22: ...e All possible options are covered by this table Faults Sources Causes Solutions Fan ID3 fan operation feedback Embedded thermistor faulty Circuit breaker Current too high Switch coil See causes Reset...

Page 23: ...S RTU Speed bds Set in accordance with the CMS speed Address 001 Different to 0 ModBus TCP insert the pCo Web card CIAT code 7119753 and connect it as described in the manual Validating the protocol o...

Page 24: ...p with the network cable or the earth braid and to properly separate the various cable families control power earth and communication bus A supervision program installed on a PC not supplied by CIAT A...

Page 25: ...e Disconnect the power supply to the pCO3 card Press the button on the pCOWeb card Keep pressing and switch the power to the pCO3 card back on The green LED on the left flashes then goes off after app...

Page 26: ...k Go to Administrator Area User name admin Password fadmin Click Configuration then pCO Com In Protocol Modbus Extended OR BACNET IP Baud rate 19200 Then the button Submit The speed baud rate must be...

Page 27: ...EN 27 1 PH HEE BOX...

Page 28: ...ielle d Applications Thermiques Corporation with a capital of 26 728 480 Bourg en Bresse Register of Trade and Companies no B 545 620 114 This document is not legally binding As part of our continuous...

Reviews: