4.9 Test mode menu
f1
Forçage des sorties
Unité sur Off
If all the controller's outputs are overridden, the alarms will not be signalled on the display.
Disconnecting the display will maintain the override and may result in damage to the hardware.
This menu can only be accessed in level 3 and with the unit off.
WARNING!
ACTIVATION OF ALL OVERRIDES IS THE PROGRAMMER'S RESPONSIBILITY
NONE OF THE SAFETY DEVICES ARE OPERATIONAL
The unit must be set to " ".
Select the output to be changed by pressing
or
. Confirm by pressing
ENTER
.
The cursor places itself below the override authorisation (free or overridden). Confirm by pressing
ENTER
.
The cursor places itself under the override value. Display the new value by pressing the
key or the
key. Confirm by pressing
ENTER
.
The unit is now in "test mode".
The overrides are cancelled when the unit is set back to "on"
Output
Parameter
Setting range
Default value
Access level
Mask
Air heater fan
State 0-10 V
0-100%
0%
3
f2
TPL fan
State 0-10 V
0-100%
0%
3
f3
Coil valve
State 0-10 V
0-100%
0%
3
f4
Fresh air damper
Damper state
Open/Closed
Closed
3
f5
Fault relays
Danger
Open/Closed
Closed
3
f6
Maintenance
Open/Closed
Closed
3
f6
4.10 Access level menu
Niveaux accès .
Niveau actuel : 1
Accès niveau 1 ->
Accès niveau 2
Accès niveau 3
Displays the current level
Visible only if the current level = 2 or 3, used to access or return to level 1
Visible only if the current level = 1 or 3, used to access or return to level 2
Visible only if the current level = 1 or 2, used to access or return to level 3
Niveaux accès .
ACCES NIVEAU 1
Retour au niveau 1 :
Non
If level 1 access selected
If yes back to access level 1
EN-17
1-PH HEE BOX