CIAS Elettronica S.r.l.
Ed. 1.2
Installation Handbook
Page
69
of
73
ERMO 482X3
PRO
t.
Select by the “function switch”
SW1 position C
. The e
nable/disable “Save Prealarm Event”
phase is activated.
To
read
the present “Save Prealarm Event” value operate as follow:
•
Rotate decimal switch
SW3
(tens column) on position 0 (the first red led
D13
becomes
ON).
•
Rotate decimal switch
SW2
(units column) on position 0 or 1: if the second red led (
D12
)
becomes ON at position 0 then the prealarm event will be not saved, otherwise (position
1) the prealarm event will be saved.
Default value 00.
To
activate
the
“Save Prealarm Event” operate as follow:
•
Rotate decimal switch
SW3
(tens column) on position 0
•
Rotate decimal switch
SW2
(units column) on position 1
•
Push the button S2.
To
disable
the
“Save Prealarm Event” operate as follow:
•
Rotate decimal switch
SW3
(tens column) on position 0
•
Rotate decimal switch
SW2
(units column) on position 0
•
Push the button S2.
u.
Select by the “function switch”
SW1 position F
. The enable/disable balanced line phase is
activated (paragraph 3.3.5).
To
read
the present balanced line value operate as follow:
•
Rotate decimal switch
SW3
(tens column) on position 0 (the first red led
D13
becomes
ON).
•
Rotate decimal switch
SW2
(units column) on position 0 or 1: if the second red led (
D12
)
becomes ON at position 0 then the balanced line is disable, otherwise (position 1) the
balanced line is active.
Default value 00 (balanced line disable).
To
activate
the Balanced Line operate as follow:
•
Rotate decimal switch
SW3
(tens column) on position 0
•
Rotate decimal switch
SW2
(units column) on position 1
•
Push the button S2.
To
disable
the Balanced Line operate as follow:
•
Rotate decimal switch
SW3
(tens column) on position 0
•
Rotate decimal switch
SW2
(units column) on position 0
•
Push the button S2.
v. To ensure that all changed parameters are saved and they will be not lost even if you turn off
the receiver,
Select by the “function switch”
SW1
position 0 and press S2.
•
The alignment procedure is closed when the radome will be closed and the tilt switch
results in vertical position.