background image

 

,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV

UHO  FRG 

UHO  FRG 

1592009030 XW271 GB_1.doc

                           

;:/  ;:/

2/4

TO START A MANUAL DEFROST

1.

Push the DEF key for more than 2 seconds and a manual defrost will start.

TO ENTER IN PARAMETERS LIST “PR1”

To enter the parameter list “Pr1” (user accessible parameters) operate as follows:

1. Enter the Programming mode by pressing the Set and DOWN key for few

seconds (

 and 

 

start blinking).

2.

The instrument will show the first parameter present in “Pr1”

TO ENTER IN PARAMETERS LIST “PR2”

To access parameters in “Pr2”:
1. 

Enter the “Pr1” level.

2. 

Select “Pr2” parameter and press the “SET” key.

3. 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.

4. Use 

X

X

 or 

W

W

 to input the security code in the flashing digit; confirm the figure by pressing “SET”. The

security code is “321“.

5. 

If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the last digit.

Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys
within 30 seconds.

NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + 

W

W

. When a

parameter is present in “Pr1” LED 

 is on.

HOW TO CHANGE THE PARAMETER VALUE

1.  Enter the Programming mode.
2.  Select the required parameter with 

X

X

 or 

W

W

.

3.  Press the “SET” key to display its value (

 and 

 LED starts blinking).

4. Use 

X

X

 or 

W

W

 to change its value.

5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.

HOW TO LOCK THE KEYBOARD

1. 

Keep the 

X

X

 and 

W

W

 keys pressed together for more than 3 s the 

X

X

 and 

W

W

 keys.

2. 

The “POF” message will be displayed and the keyboard is locked. At this point it is only
possible the viewing of the set point or the MAX o Min temperature stored and to switch
ON and OFF the light, the auxiliary output and the instrument.

TO UNLOCK THE KEYBOARD

Keep the 

X

X

 and 

W

W

 keys pressed together for more than 3s.

ON/OFF FUNCTION

By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is
switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a
monitoring system is connected, it does not record the instrument data and alarms.
N.B. During the OFF status the Light and AUX buttons are active.

TO SEE THE PROBE VALUES

1.

Enter in “Pr2” level.

2.

Select “Prd” parameter with 

X

X

 or 

W

W

.

3.

Press the “SET” key to display “Pb1” label alternate with Pb1 value.

4.

Use 

X

X

and 

W

W

 keys to display the other probe values.

5.

Press “SET” to move to the following parameter.

PARAMETER LIST

REGULATION

Hy

Differential:  (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor
Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set
point.

LS

Minimum set point limit: (-50,0°C

÷

SET; -58°F÷SET) Sets the minimum acceptable value for the set

point.

US

Maximum set point limit: (SET

÷

110°C; SET÷230°F) Set the maximum acceptable value for set point.

OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the

instrument and inhibits any output activation for the period of time set in the parameter. (AUX and Light
can work)

AC

Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart.

CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used,

for instance, when the room is filled with new products.

Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case

of faulty thermostat probe. With COn=0 compressor is always OFF.

COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of

faulty thermostat probe. With COF=0 compressor is always active.

DISPLAY

CF

Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit is
changed the SET point and the values  of the regulation parameters have to be modified

rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.

de = 0,1°C
in = 1 °C

Lod Local display : select which probe is displayed by the instrument:

P1 = Thermostat probe
P2 = Evaporator probe
P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)

Red Remote display : select which probe is displayed by the remote display (XW-REP)

P1 = Thermostat probe
P2 = Evaporator probe
P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)

DEFROST

tdF Defrost 

type:

rE = electrical heater (Compressor OFF)
rT = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on
the evaporator temperature and “dtE” value.
in = hot gas (Compressor and defrost relays ON)

EdF Defrost mode: 

in = interval mode. The defrost starts when the time “Idf” is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the compressor
is running (even non consecutively) and only if the evaporator temperature is less than the value in "SdF
(set point for SMARTFROST).

SdF Set point for SMARTFROST: (-30

÷

30 °C/ -22

÷

86 °F) evaporator temperature which allows the IdF

counting (interval between defrosts) in SMARTFROST mode.

 dtE  Defrost  termination  temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator

probe is present) sets the temperature measured by the evaporator probe which causes the end of
defrost.

IdF

Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost
cycles.

MdF  (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost

duration, when P2P = y, defrost end based on temperature, it sets the maximum length for defrost.

dFd  Display during defrost:

rt = real temperature;
it = temperature reading at the defrost start;
Set = set point;
dEF = “dEF” label;
dEG = “dEG” label;

dAd  Defrost display time out: (0

÷

255 min) Sets the maximum time between the end of defrost and the

restarting of the real room temperature display.

Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and the

restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that
might have formed due to defrost.

dPO First defrost after start-up:

= Immediately;
n = after the IdF time

dAF  Defrost delay after fast freezing: (0min÷23h 50min)  after a Fast Freezing cycle, the first defrost will be

delayed for this time.

FANS

FnC Fan operating mode:

C-n = running with the compressor, OFF during the defrost;
C-y = running with the compressor, ON during the defrost;
O-n = continuous mode, OFF during the defrost;
O-y = continuous mode, ON during the defrost;

Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator fans start.
FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe,

above which the fan is always OFF.

ALARMS

ALC Temperature alarm configuration

rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.

ALU High temperature alarm setting:

ALC= rE, 0 

÷

 50°C or 90°F

ALC= Ab, ALL 

÷

 110°C or 230°F

when this temperature is reached and after the ALd delay time the HA alarm is enabled.

ALL Low temperature alarm setting:

ALC = rE , 0 

÷

 50 °C or 90°F

ALC = Ab , - 50°C or -58°F 

÷

 ALU

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.

AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature

alarm set point and fan regulation set point, always positive.

ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and

the corresponding alarm signalling.

dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the

temperature alarm condition after the instrument power on and the alarm signalling.

EdA  Alarm delay at the end of defrost: (0

÷

255 min) Time interval between the detection of the temperature

alarm condition at the end of defrost and the alarm signalling.

dot  Delay of temperature alarm after closing the door : (0

÷

255 min) Time delay to signal the temperature

alarm condition after closing the door.

doA  Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its

alarm signalling: the flashing message “dA” is displayed.

tbA  Buzzer and alarm relay silencing: by pushing one of the keypad buttons.

n= Only the Buzzer is silenced;
y= Buzzer and relay are silenced.

nPS  Pressure switch number: (0 

÷

15) Number of activation of the pressure switch, during the “did” interval,

before signalling the alarm event (I2F= PAL).

PROBE INPUTS

Ot

Thermostat probe calibration: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the

thermostat probe.

OE   Evaporator  probe  calibration:  (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the

evaporator probe.

Summary of Contents for CIAO GEL 12

Page 1: ...ICE CREAM DISPLAY CABINET CIAO series Maintenance And Use Manual CIAM SPA Viale dei Pini 9 Petrignano d Assisi PG Italy tel 075 80161 Fax 075 8016215 http www ciamgroup it e mail info ciamgroup it...

Page 2: ...freezers and ice machines For ETL marked cabinet UL471 CAN CSA C22 2 No 120 M91 NSF ANSI 7 2009 1 4 RESPONSIBILITY CIAM spa declines any responsibility relevant to damages on persons animals and or p...

Page 3: ...cle Refrigerating gas R 404A Glasses Heated side glasses hetaed front glass Standard internal compressor Type Hermetic single phase No 1 1 1 Nominal power W 600 725 2 x 560 Power current of display ca...

Page 4: ...ong stock have not to be ascribed to the manufacturer 5 4 DISPLAY CABINET POSITION The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance so...

Page 5: ...the choice of piping diameter and insulation thickness has to be taken by specialised technical personnel who know specific parameters The choice of piping diameter and insulation thickness has to be...

Page 6: ...se the display cabinet has a dipper well it is necessary make the connection of its water outlet with the main water drain outlet besides it is necessary set a load water tube to the dipper well to th...

Page 7: ...a wet cloth weekly Additional defrost Under particular conditions of temperature and humidity the frost that normally forms on the evaporator and fans might increase in volume so leading to a faulty f...

Page 8: ...evaporator blocked by frost Verify the efficiency of the gasket seal relatively to the glass superstructure Verify that the display area is not crossed by draughts Verify that backsliders or night bl...

Page 9: ...ronics Replace digital thermostat Defrost water missing Water drain pipes are blocked Remove the obstacle Defrost cycle is not efficient Verify the efficiency of control panel slave module sensor sole...

Page 10: ...LEMENT OUTLET AIR HEATING ELEMENT REAR GLASS HEATING ELEMENT INTERNAL GLASS HEATING ELEMENT FRONT GLASS UPPER FRAME HEATING ELEMENT FRONT GLASS LATERAL LOWER FRAME HEATING ELEMENT FRONT GLASS LATERAL...

Page 11: ......

Page 12: ...L OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C n fans will switch ON and OFF with the compressor and not run during defrost FnC C y fans will run continuousl...

Page 13: ...Remote display select which probe is displayed by the remote display XW REP P1 Thermostat probe P2 Evaporator probe P3 auxiliary probe 1r2 difference between P1 and P2 P1 P2 DEFROST tdF Defrost type...

Page 14: ...ore signalling the BAL alarm message The relay outputs are switched OFF The alarm will stop as soon as the digital input is de activated CONFIGURABLE INPUT PRESSURE SWITCH PAL If during the interval t...

Page 15: ...Power supply 230Vac or 110Vac 10 Power absorption 7VA max Display 3 digits red LED 14 2 mm high Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A compresso...

Reviews: