Chubb PEFS F3 Maintenance Manual Download Page 9

 

Maintenance Manual 

9

 

 

 

PEFS F3 Maintenance Manual, Version 1.2, Feb 2018 

© Copyright 2017 Chubb Fire & Security Pty Ltd 

Where the water quality is  in doubt at a particular location  where filling activities are carried out, the use of water 
from  another  location  source  should  be  used.    Failure  to  do  so  may  result  in  rapid  deterioration  of  the  cylinder 
assembly, leading to leakage or failure to operate.  Routine service shall be undertaken more regularly where: 
 

(a)  water quality has proved to be a problem, or is likely to be a problem;  
(b)  salts are deposited in the cylinder; or  
(c)  hard water is used. 

 

System Defects 

 
Defects,  including  faulty  or  defective  components  advised  by  public  notices  or  manufacturers’  service  bulletins, 
shall be replaced, exchanged or repaired. 
 
Critical  defects  shall  be  rectified  with  the  minimum  of  delay.    Unless  alternative  risk  reduction  measures  are 
implemented  for  the  safety  of  personnel,  equipment  shall  not  be  operated  until  the  critical  defects  are  rectified.  
Critical defects shall be reported to the responsible entity and confirmed in writing within 24 h. 
 
An ‘out-of-service’ tag system should be used to indicate that the system is temporarily impaired.  Tags should be 
attached  to the  affected  equipment  for  the  duration  of  the  impairment.    Evidence  of  the  service  level  shall  not be 
applied to the service tag or label.  The inspection and the outcome shall be entered in the service records. 
 
Non-critical defects shall be rectified as soon as practicable and reported to the responsible entity. 
 

Service Records 

 
A service record at the  completion  of any scheduled  maintenance should  be  provided to the equipment owner or 
responsible entity.  The service record should contain the following information: 
 

1.  Service activities. 
2.  Defects. 
3.  Rectifications and by whom. 
4.  Date conducted. 
5.  Where modification to the system has occurred: 

a.  Updated system baseline data or fire system specification 
b.  System re-commissioning report. 

 
A service tag or label should be provided for each fire protection system to record the last level of inspection, test 
and survey performed. 
 
The level of service carried out shall be etched, embossed stamped, or indelibly marked on the tag or label in the 
box corresponding to the year and month in which the routine was performed, with a figure representing the routine 
as follows: 
 
 

Punched hole 

= commissioned/placed in-service 

 

= Six-monthly 

 

2   = Yearly 

 

3   = Five yearly 

 

4   = Recharged after use 

 
The figures shall be not less than 3mm high, and the markings shall be such that the figures are legible. 
 
When  a  new  service  label  is  provided,  the  label  shall  be  applied  adjacent  to  the  completed  label  so  that  the 
previous service history is not obscured. 
 
 

 

Summary of Contents for PEFS F3

Page 1: ...Part Number 61445 Feb 2018 VEHICLE FIRE SUPPRESSION SYSTEM Fluorine Free Foam Maintenance Manual...

Page 2: ...xing Updated annual service instructions for manual actuators Updated Cylinder Assembly details Updated C106 bracket dimensions 1 2 Reduced low cylinder pressure switch from 1600kPa to 1550kPa This ma...

Page 3: ...containers Item 7 16 System Labels Item 8 16 After Maintenance Activities 16 Yearly Service Instructions 17 Discharge Test Optional Item 9 17 Storage containers Item 10 17 Cylinder Valve Service Item...

Page 4: ...Actuation Components 35 Loss of Pressure Detection Tubing 35 Electric Solenoid Valve Assembly 35 Actuation System Fittings 36 Monitoring Components 37 Pressure Switches 37 Identification Instruction...

Page 5: ...tance or event outside of Chubb s control This warranty is conditional upon documented evidence of proper maintenance performed in accordance with the PEFS F3 Owner s Manual and Maintenance Manual by...

Page 6: ...remedies the Customer has under the Australian Consumer Law and other laws applicable to the products and services This warranty is provided by Chubb Fire Security Pty Ltd Intended use The PEFS F3 Foa...

Page 7: ...sist of pressurised cylinders containing fluorine free foam solution actuation devices to initiate discharge and a discharge network containing aspirating spray nozzles to direct the foam spray on the...

Page 8: ...at to which they were originally designed Prior to commencing any maintenance activities a pre maintenance review shall be undertaken to determine whether a the system will perform as it is intended t...

Page 9: ...on of the impairment Evidence of the service level shall not be applied to the service tag or label The inspection and the outcome shall be entered in the service records Non critical defects shall be...

Page 10: ...12 7mm OD tube Flaring tool 37 to suit 12 7mm OD tube Hand Drill type deburring tool 2 14mm Angle grinder 100 mm Drill Heavy duty 12 7 mm chuck Drill Set 1mm 13mm x 0 5mm high speed Socket set metric...

Page 11: ...actuator pressure indicators are visible and read within normal range Manual actuators a Check that all anti tamper seals and pull pins are in place and secure b Physically check that all manual actua...

Page 12: ...amage and condition b Check date of test or manufacture on storage container If over 5 years old subject the cylinder to an inspection and hydrostatic pressure test in accordance with AS 2030 5 and AS...

Page 13: ...ge Check for the presence of unprotected hazard areas particularly where a source of fuel and heat exists 23 Operational conditions Check that the detector response and extinguishing agent discharge o...

Page 14: ...control panel where applicable to its Isolation Test mode WARNING System Control Panels must remain in there Isolation Test mode during the remainder of the scheduled maintenance activities to prevent...

Page 15: ...s are designed to fail to safe That is any fault causing leakage will activate the system As such the LOP Manual actuators may be considered operational if the below listed checks are carried out 1 Ch...

Page 16: ...y holds the cabling in place f Detector locations are in correct position Refer to system design data baseline data as of last commissioning Storage containers Item 7 1 Check all cylinder valves are n...

Page 17: ...rge hose 3 from cylinder valve 4 2 Fit end cap to discharge outlet port to prevent accidental discharge 3 Remove Schrader valve cap from filler port assembly 1 4 Depress Schrader valve core to release...

Page 18: ...eplace if required Lubricate outside diameter o rings 11 and outside diameter of piston assembly 10 with Molykote 111 Do not lubricate sealing o ring 15 and check valve o ring 16 If retainer 12 was re...

Page 19: ...sembly C30 Cylinder 1 Remove Filler Plug Assembly 2 Fill system cylinder with 9 5 litres of water 3 In a 10 litre bucket a Fill with 6 litres of water b Add half 1 2 of the quantity of foam from the C...

Page 20: ...ly Method 2 Post Mixing requires mixing tool 1 Remove Filler Plug Assembly 2 Filling by Scales a Remove Over fill tube if fitted from filling port b Fill cylinder with water to required volume as per...

Page 21: ...hand for the first couple of turns before using the Nozzle Cap Tool to tighten the cap to prevent cross threading 7 Check nozzles are pointing at pre determined aiming points Refer to system design da...

Page 22: ...ate 2 Remove actuation hose from actuator connection 1 3 Remove Foil Nozzle 2 and Adaptor 3 4 Check the Foil Nozzle 2 to ensure its foil seal is intact and not damaged or ruptured Replace if required...

Page 23: ...lace Actuation system Pneumatic Item 16 Check pneumatic actuation system is intact and not damaged 1 Hoses are not worn split cut or kinked 2 Hoses have protective sleeves fitted along locations where...

Page 24: ...s WARNING Do not pressurise a cylinder that is not in test date NOTE Do not pressurise LOP systems using the schrader valve on the filler port assembly of the PEFS cylinders This will cause the cylind...

Page 25: ...cators are reading in the green zone 2 Ensure all labels are in good condition refer 6 monthly service item 8 3 Ensure control panel where fitted is reset to its normal operation mode and is no longer...

Page 26: ...4 Actuation system Check 5 Manual LOP Actuators Check 6 Detection system Check 7 Storage containers Check 8 System Labels Check 9 Discharge Test optional Discharge Time 10 Storage containers Inspect 1...

Page 27: ...MPa 3 6 MPa 3 3 MPa 3 6 MPa 3 3 MPa 3 6 MPa 3 3 MPa Total Fill 18 lt 24 lt 35 lt 50 lt 85 lt Water quantity 16 lt 21 5 lt 31 lt 44 lt 75 lt Foam quantity 2 lt 2 5 lt 4 lt 6 lt 10 lt Pressure 21 o C 17...

Page 28: ...ly Siphon Tubes Figure 8 Siphon tube Cylinder Size Siphon Tube Part Number Syphon Tube Length 2mm C23 109298 719 C30 110281 485 C45 110282 546 C65 110283 745 C106 112040 1156 Table 9 Siphon tube detai...

Page 29: ...Figure 9 C23 Cylinder Bracket Figure 10 C30 Cylinder Bracket part number 128735 part number 128736 Figure 11 C45 C65 Cylinder Bracket Figure 12 C106 Cylinder Bracket part number 128737 part number 12...

Page 30: ...Hose Size Part Number Minimum Bend Radius Temperature Rating Air Water 118097 180mm 7 40 C 71 C 118098 240mm 9 5 Table 12 Discharge hose Nozzles Figure 15 Nozzle assembly Part Number Description 46125...

Page 31: ...90 part number 115151 Nozzle kit single straight 90 part number 115152 Nozzle kit single end part number 94431 Nozzle kit double straight 90 part number 115153 Nozzle kit double straight 90 45 part nu...

Page 32: ...swivel 128995 3 4 Hose x 1 1 16 JIC f swivel 129671 1 2 Hose x 3 4 JIC m Cap Nut 112145 3 4 JIC Nut Sleeve to suit 1 2 Tube Adaptor Reducing Bushes 112146 3 4 JIC m x 1 1 16 JIC f 112144 3 8 BSP m x 1...

Page 33: ...ws 112136 3 4 JIC m f swivel 112436 1 1 16 JIC m f swivel 112138 3 8 BSP m x 3 4 JIC m 112134 3 4 JIC m 112135 1 1 16 JIC m 112139 3 8 BSP f x 3 8 BSP f 128743 45 1 1 16 JIC m f swivel 114567 45 3 4 J...

Page 34: ...017 Chubb Fire Security Pty Ltd Type Part No Description Type Welded Clamp Blocks Size Spacing 132823 Tube 0 5 112113 Hose 0 7 128818 Hose 0 7 94435 Bolt on Base to suit 132823 Size Spacing 130073 Dou...

Page 35: ...nd must therefore be replaced annually as part of the regular maintenance routine Manual LOP Actuator Figure 17 LOP Manual Actuator Part Number Description 47130 LOP Manual Actuator 47131 LOP Manual A...

Page 36: ...ble Hose Fitting Crimp 128999 1 4 Hose x 7 16 JIC f swv Crimp LOP Tubing Coupling 128763 1 4 LOP tube x 7 16 JIC m Compression AN Union LOP Tubing Cap 128764 1 4 LOP Tube EOL Compression Cap Manifold...

Page 37: ...p Size Maximum Spacing m 128819 Tube 0 5 103197 Hose 1 4 0 5 103198 Use with Grommet 103248 0 5 130078 Hose with hose protector 0 5 Grommet 103248 Grommet to hold LOP tubing Use with P Clip 103198 Wel...

Page 38: ...2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd Identification Instruction Labels part number 66534 part number 66535 part number 66536 part number 66537 part number 66137 part number 66556 par...

Page 39: ...Maintenance Manual 39 PEFS F3 Maintenance Manual Version 1 2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd APPENDIX SDS Chubb PEFS F3 Foam Concentrate...

Page 40: ...Maintenance Manual 40 PEFS F3 Maintenance Manual Version 1 2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd...

Page 41: ...Maintenance Manual 41 PEFS F3 Maintenance Manual Version 1 2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd...

Page 42: ...Maintenance Manual 42 PEFS F3 Maintenance Manual Version 1 2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd...

Page 43: ...Maintenance Manual 43 PEFS F3 Maintenance Manual Version 1 2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd...

Page 44: ...Maintenance Manual 44 PEFS F3 Maintenance Manual Version 1 2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd...

Page 45: ...Maintenance Manual 45 PEFS F3 Maintenance Manual Version 1 2 Feb 2018 Copyright 2017 Chubb Fire Security Pty Ltd...

Page 46: ...asion Corrosion in a line and not wider than 6 5 mm at the surface NOTE Line corrosion occurs most commonly at a junction with an attachment such as a foot ring Condemn where the length exceeds 75 mm...

Page 47: ...d where appropriate in accordance with the original manufacturing specification and hydraulically pressure tested in accordance with AS2337 1 Section 7 or shall be condemned Where the burned areas of...

Reviews: