Chart A – Kit Selection Guide
Grill
Disconnect
Hanger
Wall Mount
Portable
Model
Kit
Kit
Kit
Ground Fault
Cart Kit**
STAR-02A-11-F
PCN 111878
NA
NA
STAR-02A-81-F
PCN 111878
PCN 340777
NA
STAR-02A-21-F
PCN 111878
PCN 340785
NA
STAR-02A-71-F
PCN 111878
PCN 340793
NA
STAR-02A-41-F
PCN 111878
PCN 340806
NA
STAR-02A-61-F
PCN 111878
PCN 340814
NA
STAR-05A-81-F
PCN 111894
PCN 340777
PCN 340620
STAR-05A-21-F
PCN 111894
PCN 340785
PCN 340620
STAR-05A-71-F
PCN 111894
PCN 340793
PCN 340620
STAR-05A-41-F
PCN 111894
PCN 340806
PCN 340620
STAR-05A-61-F
PCN 111894
PCN 340662
PCN 340654
PCN 340814
PCN 340620
STAR-06A-83-F
PCN 340638
PCN 340777
PCN 340830
STAR-06A-23-F
PCN 340638
PCN 340785
PCN 340830
STAR-06A-71-F
PCN 340638
PCN 340793
PCN 340830
STAR-06A-43-F
PCN 340638
PCN 340806
PCN 340830
STAR-06A-63-F
PCN 340638
PCN 340814
PCN 340830
STAR-14A-83-F
PCN 340857
PCN 340777
PCN 340849
STAR-14A-23-F
PCN 340857
PCN 340785
PCN 340849
STAR-14A-71-F
PCN 340857
PCN 340793
PCN 340849
STAR-14A-43-F
PCN 340857
PCN 340806
PCN 340849
STAR-14A-63-F
PCN 340857
PCN 340814
PCN 340849
OPTIONAL ACCESSORIES
** Includes Grill(s)
4
MAINTENANCE
ELECRIC SHOCK HAZARD. Disconnect all power
before servicing or replacing heating elements.
BURN HAZARD. Hot surfaces. Allow sufficient time for
heater to cool before serviceing or cleaning heater.
The reflectors should be kept clean to obtain the maximum
radiant output.
Element Replacement
1.
Remove Terminal Box Cover.
2.
Disconnect lead wires from heater terminals and disengage box
from conduit /cable fitting.
3.
Remove safety grills (if installed).
4.
Remove retainer screw located on the reflector at the terminal end.
5.
Loosen (2), 3/8" nuts from the terminal box bracket located on the
back of the heater and slide the entire heating element assembly
out of the reflector assembly.
6.
Remove wires and jumper straps as required to replace the failed
heating element(s).
7.
Remove bulkhead fitting nuts and washers.
8.
Remove failed element and replace with a new element. Replace
only with genuine Chromalox "Arctic End" elements. Use of other
elements will cause excess temperatures inside terminal box.
9.
Place gasket on the bulkhead fitting and insert terminals and fit-
tings into the element holes in the terminal box.
10.
Place washers and nuts on bulkhead fittings and tighten.
11.
Replace wiring and jumper straps (see Fig. 1).
12.
Reassemble by following the reverse procedures
(steps 5 through 1).