HZ Series EMERGENCY TWO HEAD LED EXIT 

 

WIRING CALCULATIONS FOR VOLTAGE DROP PROTECTION 

 

IN EMERGENCY LIGHTING SYSTEMS 

 

TO DESIGN A PROPER EMERGENCY LIGHTING SYSTEM, CIRCUIT RUNS MUST BE OF SUFFICIENT SIZE TO MAINTAIN A PROPER 
OPERATING VOLTAGE TO ALL LAMPS.  MAXIMUM ALLOWABLE VOLTAGE DROP SHOULD NOT EXCEED 5%.  PROPER WIRE SIZE 
IS DETERMINED FROM THE FOLLOWING FORMULA, TABLE AND EXAMPLE SHOWN BELOW. 
 

 

 

 

 

 

 

 

L = 

CM x EI 

 

CM= 

I x 22 x L 

 

 

I x 22 

 

EI 

 

CM = WIRE SIZE IN CIRCULAR MILLS 

 

 

 

 

 

 

I = LOAD IN AMPERES (EMERGENCY MODE) 

 

 

 

 

 

 

L = LENGTH OF WIRE RUN. (UNIT TO REMOTE LOAD) 

EI = 

I x 22 x L 

 

I= 

CM x EI 

 

EI = MAXIMUM ALLOWABLE VOLTAGE DROP. (5%) 

CM 

 

L X 22 

 

 

 

USING THE ABOVE FORMULA AND HAVING CALCULATED THE CIRCULAR MILLS REQUIRED TO CARRY THE SPECIFIED LOAD AT 
A PREDETERMINED AND ALLOWABLE VOLTAGE DROP, THE FOLLOWING CHART WILL IDENTIFY THE NECESSARY WIRE GAUGE 
FROM THE CORRESPONDING CIRCULAR MILL SIZE LISTED. 
 

WIRE GAUGE 

AMPERE CAPACITY 

OHMS PER 1000 ft 

CIRCULAR MILL SIZE 

12 

20 

1.586 

6,530 

10 

25 

.9972 

10,380 

35 

.6271 

16,510 

50 

.3944 

26,250 

70 

.2480 

41,740 

 

 

 

 

 

 

 

 

 
 

EXAMPLE: 

WHAT SIZE SHOULD BE USED FOR A 6-VOLT CIRCUIT TO TRANSMIT A CURRENT OF 4 AMPERES A  
DISTANCE OF 75 FEET WITH A VOLTAGE DROP OF NOT MORE THAN 5%? 
EI = MAXIMUM ALLOWABLE VOLAGE DROP 5% OF SELECTED VOLTAGE: 
 
USING 6 VOLTS x .05 = .3 VOLTS. 
 
USING THE FORMULA AND SUBSTITUTING THE GIVEN QUANTITIES: 

 

CM = 4 x 22 x 75  = 22000 CIRCULAR MILLS NEEDED. (USE #6 WIRE) 

            

 

 

.3 

 

NOTE: 

SMALLEST PERMISSIBLE WIRE SIZE FOR SYSTEMS UNDER 50 VOLTS IS #12 FOR EMERGENCY LIGHTING EQUIPMENT 

      

UNDER ARTICLE 720-4 OF THE NATIONAL ELECTRIC CODE

 

6 VOLT 

                                                                                                                   

WIRE 

WATTS 

 

 

SIZE 

12 

24 

60 

#12 

47 

23 

#10 

75 

37 

15 

#8 

119 

59 

23 

#6 

189 

94 

38 

 

WIRING DISTANCE IN FEET 

 
 

Summary of Contents for HZ Series

Page 1: ...d metal hardware to the enclosure Do not store or place flammable materials near lamp Install only grounded wiring systems to supply this equipment CAUTION ensure lamp heads are positioned so they are aimed below horizontal CLASS I DIV 2 HAZARDOUS LOCATION GROUPS A B C AND D ZONE 2 GROUPS IIC IIB AND IIA CLASS II DIV 2 GROUPS F AND G AND CLASS III DIV 1 AND 2 INSTALLATION AND OPERATING INSTRUCTION...

Page 2: ...r is used a Connect WHITE wire to 24VDC Positive and 24VDC Negative b Use wire nuts for connection not supplied 7 Connect Battery connectors to the panel See Figures 4 and 6 8 Adjust head s as follows See Figure 3 a Rotation Loosen head nut and rotate head to desired position Retighten head nut An antirotation screw has been provided to ensure proper rotation b Angle Loosen thumb screw passing thr...

Page 3: ...hone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 INSTRUCTIONS OPERATION 1 Energize AC power to exit Unit will initiate normal power up sequence See page 4 Figure 3 Battery Connectors Figure 4 Figure 5 Figure 6 ...

Page 4: ...ating condition Rapid Flash product performing an automatic or manually initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat t...

Page 5: ...hone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 IR Remote Control optional is a hand held device that allows remote activation of diagnostic testing and silencing of the optional buzzer during fault conditions ...

Page 6: ... VOLTAGE DROP 5 CM L X 22 USING THE ABOVE FORMULA AND HAVING CALCULATED THE CIRCULAR MILLS REQUIRED TO CARRY THE SPECIFIED LOAD AT A PREDETERMINED AND ALLOWABLE VOLTAGE DROP THE FOLLOWING CHART WILL IDENTIFY THE NECESSARY WIRE GAUGE FROM THE CORRESPONDING CIRCULAR MILL SIZE LISTED WIRE GAUGE AMPERE CAPACITY OHMS PER 1000 ft CIRCULAR MILL SIZE 12 20 1 586 6 530 10 25 9972 10 380 8 35 6271 16 510 6 ...

Page 7: ... North America Corporation 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 Figure 7 ...

Page 8: ...one 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 Top Assembly Drawing For Reference only Heads Batteries Chassis assembly Lens Figure 8 Batteries Control Board Membrane switch Chassis assembly back view Figure 9 ...

Reviews: