Self Diagnostic System Operation – Emergency Light or EXIT Sign Products 

 

Normal Power Up Sequence 

 

At power up the red and green LED indicators will alternately flash for one to two seconds. Next the product will execute 

a “Power Up Quick Test” causing the green LED indicator to flash rapidly. If any faults are detected during the “Power Up 

Quick Test” these will be evident by a flashing red LED indicator.  If the audible diagnostic option has been ordered, the 

flashing red LED will be accompanied by a simultaneous beeping tone. 

(Note: A continuous rapid alternating Red/Green 

flash with rapid beeping tone indicates 277V applied to 120V input lead. TURN OFF POWER IMMEDIATELY!) 

 

Emergency Operation 

Emergency operation occurs when AC power fails. The product remains in emergency operation until AC power is 

restored or battery capacity is depleted. During emergency operation both red and green LED indicators are disabled. 

 

User Interface 

 

Green LED indicator

 

 

Slow Flash/Continuous ON = AC power present; normal operating condition 

 

Rapid Flash = product performing an automatic or manually initiated diagnostic test 

Red LED indicator 

 

Single Flash = battery fault 

 

Two Flashes = lamp failure (light bar failure – EXIT signs) 

 

Three Flashes = charger fault 

 

Four Flashes = transfer fault 

(If more than one fault condition is present simultaneously, the red LED will flash the indication pattern for each 

fault independently then repeat the cycle.) 

 

Pushbutton Test Switch

 

 

Long Press (longer than 0.5sec) transfers product to emergency operation during time the button is 

pressed. 

 

Short Press initiates self diagnostic activities as follows: 

 

One Press cancels diagnostic test presently running. 

 

Two Presses starts a one minute diagnostic test. 

 

Three Presses starts a 90 minute diagnostic test. 

 

Four Presses conducts a lamp load calibration (emergency light products only). 

 

Seven Presses initiates a system reset. 

(Note: the microprocessor will allow up to seven, one minute diagnostic tests within the first 24 hours of 

operation. Allow 24 hours of charging before performing any long duration testing.) 

 

Buzzer

 (optional)– Sounds in unison with the flashing red LED if a fault condition is present. Buzzer may be 

silenced for up to 196 hours by a short press of either the test switch or the optional IR remote control device 

“silence” button. Correcting fault condition will cancel fault notification. Lamp failure indication requires a 

manually activated diagnostic test after lamp replacement to cancel notification. 

Summary of Contents for HZ Series

Page 1: ...d metal hardware to the enclosure Do not store or place flammable materials near lamp Install only grounded wiring systems to supply this equipment CAUTION ensure lamp heads are positioned so they are aimed below horizontal CLASS I DIV 2 HAZARDOUS LOCATION GROUPS A B C AND D ZONE 2 GROUPS IIC IIB AND IIA CLASS II DIV 2 GROUPS F AND G AND CLASS III DIV 1 AND 2 INSTALLATION AND OPERATING INSTRUCTION...

Page 2: ...r is used a Connect WHITE wire to 24VDC Positive and 24VDC Negative b Use wire nuts for connection not supplied 7 Connect Battery connectors to the panel See Figures 4 and 6 8 Adjust head s as follows See Figure 3 a Rotation Loosen head nut and rotate head to desired position Retighten head nut An antirotation screw has been provided to ensure proper rotation b Angle Loosen thumb screw passing thr...

Page 3: ...hone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 INSTRUCTIONS OPERATION 1 Energize AC power to exit Unit will initiate normal power up sequence See page 4 Figure 3 Battery Connectors Figure 4 Figure 5 Figure 6 ...

Page 4: ...ating condition Rapid Flash product performing an automatic or manually initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat t...

Page 5: ...hone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 IR Remote Control optional is a hand held device that allows remote activation of diagnostic testing and silencing of the optional buzzer during fault conditions ...

Page 6: ... VOLTAGE DROP 5 CM L X 22 USING THE ABOVE FORMULA AND HAVING CALCULATED THE CIRCULAR MILLS REQUIRED TO CARRY THE SPECIFIED LOAD AT A PREDETERMINED AND ALLOWABLE VOLTAGE DROP THE FOLLOWING CHART WILL IDENTIFY THE NECESSARY WIRE GAUGE FROM THE CORRESPONDING CIRCULAR MILL SIZE LISTED WIRE GAUGE AMPERE CAPACITY OHMS PER 1000 ft CIRCULAR MILL SIZE 12 20 1 586 6 530 10 25 9972 10 380 8 35 6271 16 510 6 ...

Page 7: ... North America Corporation 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 Figure 7 ...

Page 8: ...one 855 486 2216 www chloride lighting com Signify Canada Ltd Signify Canada Ltée 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 Top Assembly Drawing For Reference only Heads Batteries Chassis assembly Lens Figure 8 Batteries Control Board Membrane switch Chassis assembly back view Figure 9 ...

Reviews: