GENERAL INSTRUCTIONS
1)
Begin the installation process by securing the unit
less battery to the mounting surface. Three
slotted vertical keyway knockouts in the housing
are to be used to attach the housing to
independent anchor supports. Use three ¼”
toggle bolts (supplied by others) minimum to
secure the unit to drywall. If mounting to hollow
concrete masonry, a minimum of two ¼” toggle
bolts must be used. When using wall recessed
wiring, the slotted, circular keyways can be used
to secure the housing to a standard junction box
for wiring purposes only. Run the wires through
center hole of housing in preparation for unit
wiring. For surface conduit wiring, there are a
total of six knockouts which can be used for
service entrance and exit.
2)
If desired, wall mounting can also be
accomplished with use of the optional mounting
shelf (See Optional Mounting Shelf and Figure
2).
Figure 1
HOOKUP INSTRUCTIONS
Standard Units:
Connect A.C. service to unit charger leads:
Blue = 277 VAC
Black = 120 VAC
White = Common
Green = Ground
1.
Connect remote lamps, if applicable, to orange
and yellow flying leads connected to
RL+ and
RL- respectively. Ensure total unit load
(including internal lamps) does not exceed unit
rating.
2.
Adjust head(s) to illuminate desired area(s).
3.
Close cover and screw shut. Ensure electrical
wires and membrane switch cable remain inside
unit and that the cover does not pinch wires when
closed. Hand tighten two thumb nuts to finalize
cover closure.
INSTALLING BATTERIES
1.
Units ship without batteries installed. For lead
units, battery wiring harnesses are already
connected to PCB assembly and connection to the
batteries is required. In the case of Nicad units,
connection of battery harness to the PCB is
required.
2.
Install and wire batteries as appropriate. (See
Page 5-8 for battery configurations)
3.
Tighten straps to secure batteries inside unit.
OPTIONAL MOUNTING SHELF
1.
If the unit is to be mounted to poles, columns or
I-Beams, use the optional mounting shelf kit and
strapping kit (ordered separately).
2.
Use four ¼” toggle bolts (supplied by others)
minimum to secure the unit to drywall and hollow
concrete masonry.
Figure 2
3.
Once the mounting shelf is installed, the unit is
ready for installation.
4.
Place unit on shelf less batteries and secure with
three (3) securing screws (supplied with
mounting shelf) to shelf threaded inserts.