ACTIVE Series User Instruction Manual

 

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS.

 

Please read and save these instructions. This manual contains important instructions for  Chloride models: 

Follow these instructions during installation and maintenance of the UPS and batteries. 

If you have a problem with the UPS, please refer to this manual before calling the Technical Support 
Department. The Troubleshooting section on page 21 addresses most UPS-related issues.

 

Licenses and Trademarks

 

MananageUPS and MopUPS are all registered trademarks of ONEAC Corporation. All other trademarks, 
product and corporate names are the property of their respective owners 

 

913-604 @ Rev. - 

 

7/06

 

A0K7XAU

A1K0XAU

A1K5XAU

ABP1K5-2

ABP3K0-2

A2K0XAU

A3K0XAU

A2K0XHU

A3K0XHU

Chloride Power Protection 
28430 N Ballard Drive 
Lake Forest, IL 60045 USA

Telephone: (847) 990-3228 
Toll Free: (800) 388-4234 
Facsimile: (800) 833-6829

Summary of Contents for ACTIVE A0K7XAU

Page 1: ...ACTIVE Series Uninterruptible Power Supply Operating Manual A0K7XAU A1K0XAU A1K5XAU ABP1K5 2 ABP3K0 2 A2K0XAU A3K0XAU A2K0XHU A3K0XHU ...

Page 2: ...l before calling the Technical Support Department The Troubleshooting section on page 21 addresses most UPS related issues Licenses and Trademarks MananageUPS and MopUPS are all registered trademarks of ONEAC Corporation All other trademarks product and corporate names are the property of their respective owners 913 604 Rev 7 06 A0K7XAU A1K0XAU A1K5XAU ABP1K5 2 ABP3K0 2 A2K0XAU A3K0XAU A2K0XHU A3K...

Page 3: ......

Page 4: ...rnal Battery Cabinets 8 Electrical preparations 9 Connections 9 Theory of Operation 10 UPS Mode 10 Battery Mode 10 Bypass Mode 10 Front Panel Display and Control 11 System Indicators 12 Rear Panel 13 UPS Start up Shutdown 15 Normal UPS Start up Procedure 15 Manual Bypass Procedure 15 UPS Shutdown Procedure 15 Remote Power Off RPO 15 Maintenance 16 UPS Storage 16 Battery Testing 16 Replacing Batter...

Page 5: ...ii ACTIVE User Instruction Manual ...

Page 6: ...nit not expressly approved by the party responsible or in FCC compliance could void the user s authority to operate the equipment The 2 3 kVA models have been tested and comply with the limits for a ClassA digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial environment The ...

Page 7: ...be kept for later reference for operation and maintenance of the UPS These instructions may be supplemented with additional sheets describing specific extensions or options Symbols The following symbols are used in this manual ATTENTION Indicates instructions which if not observed may endanger reliability of your UPS or the security of your data WARNING Indicates instructions which if not observed...

Page 8: ...witch on the equipment it must be absolutely dry An acclimatization period of at least two hours is required The equipment must be installed in accordance with the environmental conditions specified in Environmental Conditions and in Table 2 Even with all buttons in OFF position the device UPS is not isolated from the mains To isolate completely from the mains the power cord must be disconnected T...

Page 9: ...hs at 25 C without being recharged having been charged to 100 at the beginning of any such period If these conditions are not respected the performance of the battery can no longer be guaranteed It is advisable to recharge the batteries at least once every 4 months Since new batteries often do not provide full capacity after an initial charge it may be necessary to carry out a number of discharge ...

Page 10: ...the equipment Check all packaging materials to ensure that no items are discarded Remove the packaging following the sequence illustrated in Figures 1 WARNING This unit is heavy and requires two persons for safe lifting Tools Required Scissors or Knife Screwdriver Fig 1 Unpacking the UPS This UPS includes 1 UPS 1 USB Cable Mounting Hardware Tower Stands MopUPS Express Software Download Certificate...

Page 11: ...he service life of the batteries dramatically Floor Loading Taking into consideration the weight of the UPS extension battery packs and any other equipment that may be mounted in an associated rack confirm that the floor in the chosen location be capable of supporting the weight of the combined units NOTE Weights for the UPS and battery packs are shown in Appendix A Specifications Ventilation It i...

Page 12: ...our UPS should be installed last and end up on the top of all the battery units for proper cable routing ATTENTION Use all supplied mounting hardware on each UPS and external battery NEVER depend on lower devices to support other devices All mounting materials are provided to install the UPS into a rack To prepare the UPS and external batteries for use in a rack configuration first install the inc...

Page 13: ...ur 4 screws provided After mechanical installation is complete follow the instructions in the section titled Connections on page 9 to connect your UPS and external battery Mounting theTower UPS Only 1 Assemble the two sets of feet included with the UPS Fig 3 Tower Feet 2 Place the UPS between feet as shown in Figure 4 Fig 4 UPS Tower Set Up Mounting theTower UPS Plus One External Battery 1 Assembl...

Page 14: ...an one source AC input and DC input from batteries All input sources AC and DC must therefore be disconnected before carrying out maintenance work inside the UPS Connections Battery Connections WARNING Before connecting a battery pack to the UPS the circuit breaker of the battery pack must be switched to OFF After electrical connection with the UPS is established the breaker must be switched to ON...

Page 15: ...ple in which the input AC power is first converted to DC and secondarily converted back to a sine wave of a fixed frequency and voltage to supply controlled power to the load This UPS topology is used to isolate the critical load e g servers switches routers etc from a variety of power line problems including the total loss of input AC power Battery Mode In the event of a mains failure the mainten...

Page 16: ...S i e on line on battery or on bypass Two LED indicators show the current status ON or OFF of the controllable receptacle groups 1 and 2 Four additional LEDs provide error status UPS load percentage or battery charge percentage depending on if the associated front panel button is pressed Fig 9 Front Panel Display 1 Site Wiring Fault LED 8 ON LED 2 Battery Fault LED 9 Display Selector Battery Charg...

Page 17: ...two beeps After start up checks 12 turns on Start up On Battery One and five beeps After start up checks 13 turns on On Line NA On Line LED 12 is on On Bypass NA On Bypass LED 11 is on Transfer to Battery Three beeps On Line LED 12 turns off On Battery LED 11 turns on Low Battery Beep every 3 seconds 13 flashes every three seconds End of Battery Constant sound 13 is on constant Overload 110 Overlo...

Page 18: ...l Reference Ground 8 Fan 2 Input Power Connections 9 Output Receptacles 3 Controllable Receptacles 10 Interface COM3 RS232 4 Slot Interface COM 11 USB Interface 5 RPO Connection 12 External Battery Power Receptacle 6 Battery Counter Connector 13 Site Wiring Fault Indicator 7 Push Button for Phase Neutral Reversal Test 3 4 6 7 8 9 11 12 13 10 5 1 2 9 ...

Page 19: ...O Connection 13 Site Wiring Fault Indicator 6 Battery Counter Connector 14 Circuit Breaker for 3 Only 3000 VA 120V only 7 Push Button for Phase Neutral Reversal Test 15 Circuit Breaker for 9 Only 3000 VA 120V only 8 Fans 16 Circuit Breaker for 9A 3000 VA 230V only 17 Circuit Breaker for 9B 3000 VA 230V only 2000 VA 120 V Model 3000 VA 120 V Model 2000 VA 230 V Model 3000 VA 230 V Model 1 2 3 4 5 6...

Page 20: ...ng output power from the battery ATTENTION If the overload indicator is on or the LOAD indicator is beyond 100 there are too many devices connected to the UPS If only one device is connected to the UPS and the overload indicator is on then the load s power demand exceeds the rating of the UPS and a UPS with a higher power rating must be used NOTE If the UPS does not respond as above please see Tro...

Page 21: ... about batteries and the required precautions The batteries installed in the UPS and in the external battery cabinets contain electrolyte Under normal conditions the containers are dry A damaged battery may leak electrolyte that can be dangerous in contact with the skin and cause irritation to the eyes Should this happen wash the affected part with copious amounts of water and seek immediate medic...

Page 22: ... side of the front cover snaps out of position 4 Remove the left side of the front cover and place it in a safe place 5a On 700 VA 1000 VA and 1500 VA Remove one screw on the right side of the battery retention plate that is now exposed on the front left side of the UPS Disconnect battery connectors Fig 14 Removing Front Cover and Battery Retention Plate 5b On 2000 VA and 3000 VA Disconnect batter...

Page 23: ...n UPS and a workstation server Integration of the UPS as client into a network with centralized monitoring via a ManageUPSNET SNMP adapter in the slot COM Transfer of operational states to external alarm systems via voltage free contacts with interface card SIC in the slot COM The necessary communication software packages and interface cables are available as options Serial interface COM 3 The 9 p...

Page 24: ...e an installation wizard will appear Follow the installation instruction from the wizard Once MopUPS Express is installed and launched the user manual can be accessed by clicking on the Help button If further assistance is needed contact Technical Service at 800 879 5011 or email usa service chloridepower com Optional Isolated Contacts Card Below are the descriptions of the interface signals for t...

Page 25: ...es a N O contact between pins 6 and 5 and an N C contact between pins 7 and 5 The 6 5 contact closes when the battery has been depleted to the point that it can only supply current for approximately three 3 more minutes at nominal load The 7 5 contact provides a mirror function opening when the battery is low BYPASS ACTIVE This output provides an N O contact between pins 1 and 5 The 1 5 contact cl...

Page 26: ...tery Power Check the power drawn by the equipment and disconnect any short circuited or non priority devices Restart the UPS Battery LED blinks buzzer beeps A battery fault was detected during the automatic battery test Check that battery connector is properly seated Replace the battery module Battery LED blinks buzzer sounds long beep about once every hour The battery is at end of life runtime on...

Page 27: ...e conversion This provides the highest level of protection from power line disturbances available Two year warranty on power control systems Two year warranty on batteries Scalable power and runtimes Hot swappable user replaceable batteries Integrated manual and automatic bypass Comprehensive front panel control indicators Remote Power Off RPO Operates a a frequency converter ...

Page 28: ...lectable Available output voltage XAU models low voltage 120 V factory default 100 127 V user selectable XHU models high voltage 208 V factory default 200 208 220 230 240 user selectable Principle of operation On line double conversion Surge voltage withstand capability ANSI IEEE C62 41 Cat A B Crest factor 3 1 Recharge time to 90 available capacity 5 8 hours Total harmonic disortion linear load 4...

Page 29: ...8 5 15R 4 5 20R 1 L5 20R 4 5 20R 1 L5 30R IEC contact factory for IEC to NEMA adapters Port standard 1 serial 1 USB Comm slot 1 slot for SNMP Web Interface Internal battery 3 12 VYUASA NP7 12FR 3 12 VYUASA REW45 12FR 6 12 VYUASA NP7 12FR 6 12 VYUASA REW45 12FR 6 12 VYUASA NP7 12FR 6 12 VYUASA REW45 12FR Battery type sealed maintenance free lead acid VRLA Battery test Automatic once per month adjus...

Page 30: ...ttery A0K7XAU half load full load min 27 11 110 50 228 93 328 148 450 200 A1K0XAU half load full load min 19 7 76 32 152 59 228 93 323 126 A1K5XAU half load full load min 13 5 52 19 103 33 157 54 218 74 A2K0XAU half load full load min 16 8 86 44 171 61 285 90 404 135 A3K0XAU half load full load min 14 6 57 23 114 58 171 90 247 124 A2K0XHU half load full load min 16 8 86 44 171 61 285 90 404 135 A3...

Page 31: ...Chloride Power Protection 28430 N Ballard Drive Lake Forest IL 60045 USA Telephone 847 990 3228 Toll Free 800 388 4234 Facsimile 800 833 6829 www chlorideups com ...