background image

 

Page 10 of 16 

IRIS Touch 

 Quick Installation & Maintenance Guide Version 1.1 

 

The configuration menu on the Galaxy panel for the Ethernet card is found at location 56
(Communications) entry 4 (Ethernet), please enter the required information as indicated below. 

You must enter Engineer Mode to access these options. 

56 = Communication 

4 = Ethernet 

 

01= Module Config 

1 = IP Address 

- Program in the IP address for the IRIS e.g. 192.168.0.10

 

2 = Site Name 

- Leave blank 

3 = Gateway IP 

- Enter the network gateway IP address e.g. 192.168.0.1

4 = Network Mask 

- Enter the subnet mask e.g. 255.255.255.0

Note: If you are using a DHCP address then leave all “Module Config” addresses blank

02 = Alarm Reporting 

1 = Format    

- Set to SIA level 3 

 

2 = Primary IP  

 

 

1 = IP Address 

- Set this to the IP address of the Monitoring Centre 

e.g. 80.176.196.135 

4 = Account No.         

- Enter in the account number for the Monitoring Centre.

 

03 = Remote Access 

1 = Access Period  

- Set to 4 Any Time 

2 = Mode  

- Set to Direct Access if making call into site from Remote 
Service Suite for Upload/Download.

- Set to MGR Authorise if making the call from site to 
Remote service suite for upload/download connection and 
enter the Call Back IP1 address for the Secure Apps 
Remote Service Server, or the Honeywell RSS 
Communication Server e.g.  80.176.196.135

 

9 = Encrypt    

1 = Alarm Report 

- Set to Off 

2 = Remote Access 

- Set to Off 

 

After you have entered in the relevant information exit Engineer Mode and the panel should now detect 2 
new RS485 modules (Comms Mod 4 & Keypad 15). 

If the new modules are not detected then you may need to power off the Galaxy panel, check the dialler 
connections, and power back on. 

Now go back into Engineer Mode and select the menu option sequence 56.04.05 ‘ENGINER TEST’ and send 
the test alarm. Check to see if this test alarm has been received by the monitoring centre

You can now perform your alarm signals commissioning and sign off required by the monitoring 
(ARC).  

Note: If you are required to default the IRIS Touch and start again you can do this by setting the primary 
IP address within the Galaxy menu 56.04.02.02 to an IP address of 127.0.0.1.  

 

 

nel for the Ethernet card is found at location 56 

(Communications) entry 4 (Ethernet), please enter the required information as indicated below.  

Program in the IP address for the IRIS e.g. 192.168.0.10 

Enter the network gateway IP address e.g. 192.168.0.1 

Enter the subnet mask e.g. 255.255.255.0 

Note: If you are using a DHCP address then leave all “Module Config” addresses blank

 

Set this to the IP address of the Monitoring Centre  

Enter in the account number for the Monitoring Centre. 

Set to Direct Access if making call into site from Remote 

Service Suite for Upload/Download. 

GR Authorise if making the call from site to 

Remote service suite for upload/download connection and 
enter the Call Back IP1 address for the Secure Apps 
Remote Service Server, or the Honeywell RSS 
Communication Server e.g.  80.176.196.135 

ode and the panel should now detect 2 

may need to power off the Galaxy panel, check the dialler 

ode and select the menu option sequence 56.04.05 ‘ENGINER TEST’ and send 

centre (ARC). 

You can now perform your alarm signals commissioning and sign off required by the monitoring centre 

Note: If you are required to default the IRIS Touch and start again you can do this by setting the primary 

 

  

IRIS Touch 

 Quick Installation & Maintenance Guide Version 

 

TTL connections (Texecom Premier Range)

 

Ordered from Chiron 

 

Description  

= Texecom RS232 Lead 

Part No  

 

= Tex600  

6.4.

 

GSM SIM card (IRIS Touch 600 & 640) 

If you are using the GSM or GPRS connection then insert the GSM SIM card into the GSM SIM card holder

 

 

 

Version 1.1 

Page 7 of 16 

 

into the GSM SIM card holder. 

Summary of Contents for Iris Touch

Page 1: ... www chironsc com CHIRON SECURITY COMMUNICATIONS AG BAARERSTRASSE 19 6300 ZUG SWITZERLAND The information contained is supplied without liability for any errors or omissions No part may be reproduced or used except as authorized by contract or other written permission The copyright and foregoing restriction on reproduction and use extend to all media in which the information may be embedded 2014 C...

Page 2: ...s not exceed a safe value 42 4V peak or 60V dc maximum The interfaces on the IRIS Connect have the following safety classifications Power Interface SELV for connection to a DC supply Inputs SELV for connection to alarm output pin Conformance European Directives The IRIS Connect complies with the following European Directives 1999 5 EC Radio Telecoms Terminal Equipment Directive 2006 95 EC Low Volt...

Page 3: ...hronisation Quad band GSM 850 900 1800 1900 MHz SMA socket for GSM antenna connection Loss of registration with network 1292 Diagnostic Reflashing 10001 Upload Download Note For Radio Telecoms Terminal Equipment Directive the power cable needs to be no longer than 3 meters in length 106mA 12V DC condensing IRIS Touch Quick Installation Maintenance Guide Version 1 Introduction The IRIS Touch offers...

Page 4: ... yellow flashing some trouble events being reported 7 1 Confirm current status The IRIS Touch will indicate the current status via the LEDs as per the information below For further information please refer to the IRIS Touch Engineer Manual available from http www chironsc com downloads_security html LED Colour Indication SYS Flashing 0 5s on 0 5s Off Shows dialler is operational SIM On Dialler is ...

Page 5: ...n setting for the latest Texecom Premier Elite range if you pload download connections via tex then please refer to the IRIS Texecom Premier Installation manual or IRIS Remote Service App http www chironsc com downloads_security html monitoring centre or Customer i e Fast Format Contact ID or SIA level 2 3 onitoring centre in a 12 digit format Leave blank as the IRIS System will receive the second...

Page 6: ...Molex connector the power cable must be no Section 3 Board Configuration Connect the Ethernet cable from ETH1 to the local IP router switch or socket that has been bar GSM antenna connections are optional and depend on the panel connection method to be used Touch RS485 connection is for Honeywell Galaxy panels and the Serial TTL header is for For alternative selections for other panel connection p...

Page 7: ...alarm Check to see if this test alarm has been received by the monitoring centre You can now perform your alarm signals commissioning and sign off required by the monitoring ARC Note If you are required to default the IRIS Touch and start again you can do this by setting the primary IP address within the Galaxy menu 56 04 02 02 to an IP address of 127 0 0 1 nel for the Ethernet card is found at lo...

Page 8: ...n ensure you configure the alarm panel first as this will transmit configuration to the IRIS For more details on the alarm panel integration download the full panel installation manual from http www chironsc com downloads_security html Connect the board s Micro USB connector to a laptop PC running the IRIS Toolbox software Download the IRIS ToolBox user guide from http www chironsc com downloads_s...

Reviews: