background image

NQ2 Series Electromagnetic Starter

06

Table 5 Cross-sectional area of connecting wires of the main circuit

0 I≤8

8 I≤12

12 I≤20

20 I≤25

25 I≤32

32 I≤50

50 I≤65

65 I≤85

85 I≤100

Rated operating current of motor, I (A) 

Cross-sectional area of connecting wires of main circuit (mm²) 

1

1.5

2.5

4

6

10

16

25

35

4

Maintenance

Check whether the thermal relay inside the starter operates reliably on a regular basis (once a month) 

by  adjusting  the  current  dial  and  reducing  the  setting  current  until  the  relay  operates.  Then,  restore  the 
current dial to the original position. 

Note: Do not dismantle and repair the product at will. Once the product is found damaged, replace it 

immediately.

Table 6 Examples of Fault Analysis and Troubleshooting

Cause anaylsis

Troubleshooting method and precautions

Symptoms

Fine tune the current dial so that the product’s set 
current matches the actual current of the motor.

The setting current value of thermal relay is smaller 
than the actual operating current of the motor.

Inspect the installation site and troubleshoot to 
prevent the product from being placed in an 
environment where there is strong shock or 
viberation.

Strong shock or viberation

The motor start requires a certain interval, with 
frequency no more than 30 times per hour.

Frequent starts of the motor

Choose standard wires according to Table 5.

The cross-sectional area of connecting wires of the 
main circuit is too small.

The starter 

mis-operates 
before being 

overloaded

The setting current value of thermal relay is bigger 
than the actual operating current of the motor.

Fine tune the current dial so that the product’s set 
current matches the actual current of the motor.

The cross-sectional area of connecting wires 
of the main circuit is too big.

Choose standard wires according to Table 5.

The starter 

fails to 

operate after 

being 

overloaded

The wiring of the starter becomes loose or falls

The coil voltage is too low or voltage fluctuation is 
too big.

The setting current value of thermal relay is too 
small which leads to the failure of product reset.

Tighten the connecting screws and check whether 
the screws are loosen before use.

Increase the power supply voltage or add stabilized 
voltage equipment.

Fine tune the current dial toward the bigger current 
direction.

The starter 

fails to 

operate

Summary of Contents for NQ2 Series

Page 1: ...NO 2020 04 Standard IEC EN 60947 4 1 User Instruction NQ2 Series Electromagnetic Starter ...

Page 2: ...n and maintenance Installation in any damp condensed phase environment with inflammable and explosive gas is forbidden When the product is being installed or maintained the power must be switched off You are prohibited from touching the conductive part when the product is operating ...

Page 3: ...Altitude Pollution class installation category 5 40 average temp not exceeding 35 within 24h 40 RH not exceeding 50 and may reach 90 at 20 No influence below 2 000m Class 3 Ⅲ Table 2 Key Technical Parameters of Starter I AC 3 660V 380V 220V Model Conventional free air thermal current of shell frame Ith A Rated operating current of shell frame Ie A Rated power control of shell frame Pe kW AC contac...

Page 4: ...le 3 Key Technical Parameters of Starter II Model Use type Rated insulation voltage Ui V Rated impluse withstand voltage Uimp kV NQ2 15 1 4 NQ2 15N 1 4 NQ2 15NB 1 4 NQ2 15P 1 4 NQ2 33 1 2 NQ2 33P 1 2 85 110 Us 20 75 Us 50 IP40 Eight hour duty Uninterrupted duty Intermittent periodic duty Main circuit AC 3 AC 4 auxiliary circuit AC 15 690 6 1200 300 600 300 50 10 100 20 1000 50 10 100 600 100 AC 3 ...

Page 5: ...re Installation size D E 116 207 127 60 150 176 207 127 130 150 176 207 127 130 150 116 207 138 60 150 167 296 162 105 205 167 296 172 105 205 3 6 See Fig 1 Φ 3 6 See Fig 2 Φ 4 6 2 See Fig 3 Φ 4 6 2 See Fig 4 Φ n A D C B E B C A D n φ E φ Figure 1 Outline and installation size of NQ2 15 15N 15NB Figure 2 Outline and installation size of NQ2 15P Figure 3 Outline and installation size of NQ2 33 Figu...

Page 6: ...set button Test button 2 T1 98 97 96 95 NC NO 4 T2 6 T3 Reference point Manual reset Automatic reset Figure 5 Panel layout of the thermal relay 3 Starter wiring diagram When the product leaves the factory the control circuits are wired on the premises that the voltage of the starter is the same as that of the main circuit Once the main circuit is powered on the starter can operate without addition...

Page 7: ...g screws clockwise Figure 10 Starter installation diagram Note 1 The connecting wires of the incoming and outgoing lines of the main circuit must be single core PVC insulated copper cables with prefabricated terminal whose cross sectional area is specified in Table 5 the cross sectional area of connecting wires of the auxiliary circuit should be 1mm Tighten all the screws during wiring to prevent ...

Page 8: ...prevent the product from being placed in an environment where there is strong shock or viberation Strong shock or viberation The motor start requires a certain interval with frequency no more than 30 times per hour Frequent starts of the motor Choose standard wires according to Table 5 The cross sectional area of connecting wires of the main circuit is too small The starter mis operates before bei...

Page 9: ...r IEC EN 60947 4 1 Check 18 07 NQ2 Series Electromagnetic Starter 5 Environmental Protection In order to protect the environment the product or product parts should be disposed of according to the industrial waste treatment process or be sent to the recycling station for assortment dismantling and recycling ...

Page 10: ...ctromagnetic Starter User Instruction Zhejiang Chint Electrics Co Ltd Add No 1 CHINT Road CHINT Industrial Zone North Baixiang Yueqing Zhejiang 325603 P R China E mail global sales chint com Website http en chint com ...

Reviews: