
Chapter 5 Function Parameter Simple List
SVF-G7 Series Frequency Inverter Operation Manual
91
Function
Code
Name
Setting
Scope
and
Introduction
Factory
Defaults
Modify Page
0:
Disabled
1:
Enabled
Fb.02
Motor
overload
protection point
20.0
~
120.0%(motor
rated current)
100.0%
√
162
Fb.03
Bus-wire over
voltage at stall
110
~
150%
130%
√
162
Fb.04
Auto
current
limiting
threshold
100
~
200%
170%
√
162
Fb.05
Frequency
decrease rate in
current limiting
0.00
~
50.00Hz/s
0.00
Hz/s
√
162
Fb.06
Auto
reset
times
0
~
3
0
√
163
Fb.07
Fault
automatic
reset
interval time set
0.1
~
100.0s
1.0s
√
163
Fb.08
Type of third
latest fault
E000:No fault
E001:IGBT
shorted
protection
E004:Over-current
in
accelerating process
E005:Over-current
in
decelerating process
0
○
164
Fb.09
Type of latest
fault
0
○
164