6.7.3 Digital parameters
FNC code
……
Applicable function code,R/W
……
R:READ
,
W:WRITE
Reference
No.
FNC
code R/W DATA
Setting range
(communication range) Default
Details
101
01
05
R
W
Auto-tuning
Stop / Start
(0/1=[FF00h])
in[ ], FNC code is at 05.
Stop
(0)
The most appropriate PID constants
will be calculated automatically and
be set by the instrument by itself.
0=AT stop or End
1=AT start or AT Execution
During “Ready”, cannot be execute.
During 2-position control, cannot be
execute
6.7.4 Digital input data (only reading)
FNC code
……
Applicable function code,R/W
……
R:READ
,
W:WRITE
Reference
No.
FNC
code R/W DATA
Details
10004 02 R
RJ
error
0= normal
1=RJ error occurrence
10117
Event1status
0= event OFF 1= event ON 0= during stand by,event OFF
10118 Event1status
0
0
1
10119
Event2status
0= event OFF 1= event ON 0= during stand by,event OFF
10120
02 R
Event2status 0
0 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
EV2
EV1
Event OFF
→
0 0 0 0
Event
ON
→
0 1 0 1
30142 04 R
Event
status
during standby,
event OFF
→
1 0 1 0