DB630E-Ramp Instruction Manual

* This controller is designed for heat treatment market

Ver. 2014/7

PV : Process Value
(Current Temperature)
SV : Set Point
(Current Target Set Point)
Percentage of Output

No sensor connection

-----

The controller will begin to ramp to the set point

and will be display this mark [ 

 ].

If the controllers is no display [ 

 

] then it is

not ramping!

A. To run the controller

* Control sample

* This is asking for a value 

RATE

 to be chosen for Ramp Rate.

1 Press [ > ] key to show under cursor.
2 Using [ △ ] , [ ▽ ] keys to change the 

value 

to the desired

Ramp Rate. Blinking the changed value. ( Value/Hours )

3 Make sure to press [ENT] key to confirm.

* If you want to straight to Set Point, must be set "0".

* This is asking for a

 SP

 value to be chosen for the End-Set-Point.

Manual Output

Home Display

1 Press [ > ] key to show under cursor.

(0 to 100%)

PV/SV

2 Using [ △ ] , [ ▽ ] keys to change the value to the End Set Point.
3 Blinking the changed value. Make sure to press [ENT] key to confirm.

* When blinking "RUN" at the 

status

, press [ENT] key to start ramping

from the input temperature to the set point at the chosen ramp rate.

Ramp Rate

* Press [MODE] key to only return to HOME display.

Ex. (400F/Hour)

* While the controller is running, you can use following command.

"

RUN

" : Run the controller that is paused.

"

SKIP

" : Skip to the End Set Point of ramping control.

"

PAUSE

" : Pause the current set point.

"

OFF

" : Turn the controller OFF.

End Set Point

B. To manual out put mode.

Ex. (800F)

* This indication is "Manual Output Mode".

1 The MAN indication LED is 

ON

.

2 The percentage can be changed any time using [ △ ] , [ ▽ ] keys.
3 You can return to automatic control mode by pressing and

Current Status

holding [ > ] key for 3 seconds. 

Run/Off/Pause/Skip

* For the example if the controller percentage is set to 50% the cycle

will be on and off per approximately 4 sec. If the controller
percentage is set to 75% the cycle will be on for approximately
6 sec. and will be off for approximately 2 seconds.

Operation chart

Show under cursor for selecting the values manually.

Return to HOME display

RUN

800F

77F

Display

PAUSE

Blink

1

Solid

2

Solid

MAN

Solid

RA

RUN

Solid

PAUSE

Blink

LED

Solid

Hold

3 sec.

Any parameter changes, make sure to press [ENT] Key to confirm

Change value and parameters

Change to "Manual output mode"

Additional Notes

Additional Notes

Do This

Do This

Display

1. Press

2. Press

3. Press

Display

Status

OFF

Go to next parameters

Key Feature : There are five keys on the face of the DB630 controller

PAUSE the controller by DI

Alarm 2 Active

Alarm 1 Active

 Output 100%

 Output   0%

-----

 Output   50%

----------

RAMP Model (Stay ON)

MANUAL output mode is ON

PAUSE the controller

RUN the controller

Status

 Hold

 Hold

400F / 

A

B

Current 
Temp

A

B