- 97 -
8-26. System Settings “System”
The system related settings such as enabling/disabling settings are available.
1. Enabling and disabling settings
By entering a password, you can “disable a setting change by keys (Key Lock)”, “clear memory (Initialize)”,
“disable/enable zero or span adjustment for printing position (Adjust of Rec position)” or “disable/enable input adjustment
(Input Correction)”. Set these items as a recovery process when the unit does not function properly due to misoperation or
other reasons.
2. Output mode settings
Alarm output mode can be set. The settings are common to all relay No. Default setting is Norm.Open mode (normally
non-excitation state, at the alarm activation excitation state). Terminal configuration differs depending on the alarm output
specification.
1) Mechanical relay ‘a’ contact output
Relay mode
Power OFF
Alarm reset
Alarm activation
Norm.Open
Norm.Close
2) Mechanical relay ‘c’ contact output
Relay mode
Power OFF
Alarm reset
Alarm activation
Norm.Open
Norm.Close
N.O
COM
N.C
N.O
COM
N.C
N.O
COM
N.C
N.O
COM
N.C
N.O
COM
N.C
N.O
COM
N.C
N.O
COM
N.O
COM
N.O
COM
N.O
COM
N.O
COM
N.O
COM
When Key Lock is enabled, settings of all items cannot be changed.
The message “Key locking …..” is displayed when you try to register a parameter.
However, checking of setting items is available.
Key operation
Note 3
The default password is “3571”. This password
cannot be changed.
Default password
Note 1
When the memory clear (Initialize) is executed,
parameters will be reset to default values.
This cannot initialize the adjustment data
(zero/span calibration).
Memory clear
Note 2