Page 23 of 43
3.s
Chimney Design
Must comply with all current building legislation and either be certified by HETAS or by your
local building control department. A flue should achieve a min of 12 Pa flue draught.
Flue height (domestic)
Building regulations state this should be 4.5 metres from the top of the chilli billie to the
termination of the flue. A smoke draw test should be carried out during commissioning.
Flue height (glamping/leisure)
In single floor glamping /leisure accommodation, there may be situations where this can
be lower, if 12 Pa can be achieved. The min flue height that can be used is 2 metres (Hetas
TN0023v1.0). However as well as achieving 12Pa consideration must be made to protecting
the surface of the accommodation and to ensure combustion products are safely dispersed
(J2 discharge of products/J4 protection of building). A smoke draw test should be carried out
during commissioning.
Flue diam for CB with smoke control adaptation (domestic)
125mm from top of the stove using a 4-5” stepped adaptor or chilli billie starter pipe leading
to double skinned min 125mm internal diameter. Max length of single wall flue is 1800mm, but
must be double skinned as exits the room Single wall pipe connecting pipe should comply with
BS EN1856-2. This info should be marked on the connecting dataplate or DoP. Double walled
flue should comply with BS EN 1856-1. Min designation for solid flue is T450 N2 D3 Gxxx.
Flue diam for CB with no smoke control adaptation (domestic)
125mm leading to double skinned min 150mm internal diam.
Bends in the flue (domestic & glamping/leisure)
Avoid where possible especially with shorter flue as draw will be effected.
Flue section sockets (domestic & glamping/leisure
Must face upwards.
Joints (domestic)
Should be sealed with fire cement and mechanically fixed with rivets or self tapping screws.
Joints (glamping/leisure)
Should be sealed with fire cement and mechanically fixed with rivets or self tapping screws.
This particularly important in structures with canvas rooves so that the flue cannot be
disturbed during adverse weather conditions.
www.
chilli
penguin.co.uk
Flue diam for CB with smoke control adaptation (glamping/leisure)
125mm from top of the stove using a 4-5” stepped adaptor or chilli billie starter pipe leading
to double skinned min 125mm internal diameter. Max length of single wall flue is 1800mm, but
must be double skinned as exits the room Single wall pipe connecting pipe should comply with
BS EN1856-2. This info should be marked on the connecting dataplate or DoP. Double walled
flue should comply with BS EN 1856-1. Min designation for solid flue is T450 N2 D3 Gxxx.
Flue diam for CB with no smoke control adaptation (glamping/leisure)
125mm leading to double skinned min 150mm internal diam.
Summary of Contents for Chilli Billie
Page 1: ...www chillipenguin co uk CSP 9768 11 2020 Installation and Operating Manual The Chilli Billie...
Page 2: ...Thelittlestove withabigheart The Chilli Billie Wood only St f Fach Gyda Chalon Fawr...
Page 8: ...Theplans technicaldetails Page 06 10 Section 2 Page 06 of 43...
Page 13: ...Installation instructions Page 11 24 Section 3 Page 11 of 43 www chillipenguin co uk...
Page 27: ...Instructionsforuse Page 25 31 Section 4 Page 11 of 43 www chillipenguin co uk...
Page 34: ...Maintenance Page 32 39 Section 5 Page 32 of 43...
Page 42: ...Page 40 43 Efficiency CElabels Guarantee Section 6 Page 40 of 43...