Chapter
5Maintenance and Checkup
58
5.6.2
Error/Warning Table
Priority
Error No.
Error/warning
Description
ERROR
lamp
Device
operation
Action
High
Low
ERR03
Rotational
frequency
error
Motor is not running.
Lit
Remains
operational
Follow the remedies for
②
in
(
Page 59
).
ERR04
Internal
temperature
error
Temperature around the
blower is too high.
Lit
Stop
Follow the remedies for
②
in
(
Page 59
).
ERR06 Pressure error
Operation continued at
low pressure for more
than preset period.
Lit
Stop
Follow the remedies for
②
in
(
Page 59
).
ERR07
F-RAM write
error
Cannot write to F-RAM. Flashing
Remains
operational
Contact CHIKO AIRTEC.
ERR08
Communication
error
BCC judgment
mismatch
Flashing
Remains
operational
Contact CHIKO AIRTEC.
WARN1
Internal
temperature
high
Temperature around the
blower is close to the
error threshold.
Flashing
Remains
operational
Follow the remedies for
②
in
(
Page 59
).
WARN2
Filter
replacement
time limit
expired
Operation continued at
low air volume for more
than preset period.
Flashing
Remains
operational
Follow the remedies for
③
in
(
Page 59
).
WARN3
Inadequate
pressure
(suction)
Suction pressure is low. Flashing
Remains
operational
Follow the remedies for
②
in
(
Page 59
).
WARN4
Inadequate air
volume
Air volume is reduced by
filter clogging.
Flashing
Remains
operational
Follow the remedies for
③
in
(
Page 59
).
WARN5
Exhaust
pressure error
Exhaust pressure is too
high.
Flashing
Remains
operational
Follow the remedies for
③
or
④
in
(
Page 59
).
WARN6
Initial pressure
unregistered
Initial pressure is not
registered yet.
Flashing
Remains
operational
Register initial pressures.
(
Page 48)
WARN7
Battery
voltage low
Remaining battery level
is low.
Flashing
Remains
operational
Replace the button battery.
(
Page 55)
Summary of Contents for CBA-1500AT3-HC-DSA-V1
Page 6: ...1 4 1 4 2 OFF 1 5...
Page 7: ...1 CMN023 005 Translation of the original instructions 5 1 6...
Page 8: ...2 6 2 2 1 200V 220 230V CE 1 1 2 1 1 HEPA 1 3m 200V 1 220 230V CE 1 1...
Page 12: ...2 10 2 4 3 OP kPa SP kPa DP kPa EP kPa Blower Runtime h 18 Total h Moter...
Page 13: ...3 CMN023 005 Translation of the original instructions 11 3 3 1 3 1 1 0 40 80 RH REMOVE 1 1 1...
Page 14: ...3 12 1 2 2 3 4 OFF ON 1 A OFF 40 50 A 2...
Page 22: ...5 20 5 5 1 WARN2 1 5 1 1 1 1 1 2 2 1 3 1 4 2 1...
Page 24: ...5 22 3 ACC 4 5 6 5 2 1 Littell fuse 218 250V 15A 1 2 3 ACC...
Page 28: ...5 26 5 7 EL ON ON 5 2 22 1 2 3 4 1 4 ON OFF 30 1 2 1 2 5 1 20 5 1 20 5 1 20 5 1 20...
Page 29: ...6 CMN023 005 Translation of the original instructions 27 6 6 1 6 1 1...
Page 30: ...6 28 1 5V 0 2V LOW DC 1 2...
Page 34: ...7 32 7 3 7 3 1 CBA 1500AT3 HC DSA V1...
Page 35: ...CMN023 005 Translation of the original instructions 33 12 7 2 7 2 31...
Page 36: ...34...
Page 69: ...MEMO...