R3250Hz Universal Series Technical Manual
97
GD Chigo Heating & Ventilation Equipment Co., Ltd.
6.10 CUA-55HVR4S
MODEL
CUA-55HVR4S
HEATING
OUTDOOR CONDITIONS
Indoor Conditions
24ºC D
18ºC W
15ºC D
14ºC W
7ºC D
6ºC W
3ºC D
2ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-14ºC D
-15ºC W
15ºC
Capacity kW
17.23
17.09
17.03
16.54
15.81
15.58
13.84
Input kW.
5.99
5.43
5.31
5.24
5.12
5.07
4.83
18ºC
Capacity kW
17.06
16.97
16.91
16.43
15.72
15.46
13.96
Input kW.
6.11
5.55
5.39
5.31
5.19
5.15
4.91
20ºC
Capacity kW
16.97
16.86
16.80
16.31
15.61
15.38
13.84
Input kW.
6.19
5.63
5.51
5.43
5.31
5.27
5.03
22ºC
Capacity kW
16.89
16.74
16.69
16.20
15.49
15.26
13.76
Input kW.
6.30
5.75
5.59
5.51
5.39
5.35
5.12
27ºC
Capacity kW
16.51
16.63
16.57
16.08
15.38
15.15
13.64
Input kW.
6.42
5.83
5.67
5.59
5.51
5.47
5.19