DIGITAL CONTROL ALARMS
N.B. OPERATIONS MARKED
◼◼
MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL
APPROVED THE MANUFACTURER
DISPLAY
FLASHING WARNING
NOTES
Possible root causes
Observations
Dryer is working OK
n/a
n/a
Warning icon NOT
fashing, label P1 flashing Fan control probe failed
◼◼
replace probe
Warning icon NOT
fashing, label P2 flashing
PDP Temp probe failed
◼◼
replace probe
Warning icon NOT
fashing, label H2 flashing High PDP call for service
◼◼
refrigerant leak
◼◼
flow rate / inlet
◼◼
temperature
exeeding the limit.
Warning icon NOT
fashing, label L2 flashing
Low PDP call for service
◼◼
hot gas by pass
valve out of order.
◼◼
ambient temperature
lower then limits
EE ALARM
EE alarm is shown when internal EPROM errors happens, if this warning will appear, the dryer will stop running. The error can be reset by pressing one
of the four buttons of the controller, anyway please replace the controller itself.
NOTE: In case of EE alarm please contact your tech support.